PRODUCT FAMILY: FSK II + - OPERATING AND MAINTENANCE MANUAL22 PRODUCT FAMILY: FSK II + - OPERATING AND MAINTENANCE MANUAL 22
1VSR630206EN – en – EDO-D0002852– Instruction manual – 2021.10 Design and specification are subject to change without notice
7.2.2.2. Version: Internal connection
“Umbilical Cord”. This shielded cable is
prefabricated and factory tested. This cable is
Allways disconnect the shielded multicore
cable on the pole side.
multiple connector and must simply be connected
“X” and “Y”.
—
7. Assembly & Commissioning
The orientation is choosen by the customer or in
default position (43 for unipolar, 43 & 34 for
line connections, a special Al-Cu bimetal
must be used to protect the Al high-voltage
terminals against corrosion.
IMPORTANT!
If the customer decides to change the orientation
Tools: Torque wrench M12= 84Nm / Abrasive
paper / Solvent / Contact grease.
After disassembling step, ensure the loosen
parts (screws & washers) are in a safe and tidy
place & will not be lost
With copper connections, use solvent to clean
the contact surfaces, apply a thin layer of grease
and then mount the connections with the screws.
With Aluminium connections, you have less than 1
minute after cleaning to avoid oxidation. Abrade
the contact surfaces & clean them with solvent,
apply a thin layer of grease and then mount the
connections with the screws.
7.2.3. High-Voltage connections
connections or cable supports are to be provided.
Max. force on the high-voltage terminals in
the 3 main loading axes: Fmax <30Kg.
more details on connections mounting
Cable
exit « Y »
Cable
exit « X »