PRODUCT FAMILY: FSK II + - OPERATING AND MAINTENANCE MANUAL22 PRODUCT FAMILY: FSK II + - OPERATING AND MAINTENANCE MANUAL 22
1VSR630206EN – en – EDO-D0002852– Instruction manual – 2021.10 Design and specification are subject to change without notice
7.2.2.2. Version: Internal connection

Umbilical Cord. This shielded cable is
prefabricated and factory tested. This cable is

Allways disconnect the shielded multicore
cable on the pole side.

multiple connector and must simply be connected


X” and “Y”.
7. Assembly & Commissioning
 
 
 
 

The orientation is choosen by the customer or in
default position (43 for unipolar, 43 & 34 for



 
line connections, a special Al-Cu bimetal
must be used to protect the Al high-voltage
terminals against corrosion.
IMPORTANT!
If the customer decides to change the orientation


 Tools: Torque wrench M12= 84Nm / Abrasive
paper / Solvent / Contact grease.
 After disassembling step, ensure the loosen
parts (screws & washers) are in a safe and tidy
place & will not be lost
 With copper connections, use solvent to clean
the contact surfaces, apply a thin layer of grease
and then mount the connections with the screws.
 With Aluminium connections, you have less than 1
minute after cleaning to avoid oxidation. Abrade
the contact surfaces & clean them with solvent,
apply a thin layer of grease and then mount the
connections with the screws.
7.2.3. High-Voltage connections




connections or cable supports are to be provided.
Max. force on the high-voltage terminals in
the 3 main loading axes: Fmax <30Kg.

more details on connections mounting
Cable
exit « Y »
Cable
exit « X »