Tension Electronics PFEA111/112, User Manual
Section 3.12.5 Set Wrap Gain
3BSE029380R0101 Rev C 3-17
• By calculation (Menu EnterWrapGain)
Wrap Gain is a scaling factor which corresponds to the ratio between Web Tension (T) and 
the force component (F
R
) from web tension that is acting in the load cell measuring 
direction.
The Wrap Gain range is 0.5 - 20. If you try to set the wrap gain outside this range, the 
message “WrapGainTooLow” or “WrapGainTooHigh” will be shown on the display. 
The wrap gain can be set with a resolution of 0.01. 
Examples describing the principle of calculating Wrap Gain:
See calculation of Wrap Gain in Appendix (B, C, D, E, F or G) for installed load cell type.
T
T
T
T
T
T
F
R 
F
R 
F
R 
 
F
R 
= 2T F
R 
= T F
R 
< T
Installations where F
R
is lower than T
Wrap angle
Wrap angle
Wrap gain = 0.50 
Wrap gain =  = 0.50
Wrap gain = 
= = 1.00
Wrap gain = 
(Min. value of Wrap Gain)
Wrap gain = 
Wrap gain = > 1 
(Max. permitted value 
Wrap gain 
Wrap gain = 1.00
 
T
F
R
T
2T
T
F
R
T
T
T
F
R
of Wrap Gain is 20)