43 2TLC172001M0211_A
- The PLC program in IDFIX-PROG can be loaded into flash memory by pressing the K button
in the same way as self programming over the CAN bus. This can be done when Pluto
displays error message Er20 (No program loaded), Er24 (Erroneous PLC program) or Er31
(IDFIX-PROG program mismatch).
Programmable identifiers (IDFIX-RW and IDFIX-DATA) can for example be used where it is
required to deliver units with the same PLC program e.g. for a special machine or safety
application.