45 2TLC172001M0211_A
12 Cleaning
The front plate can be cleaned by a dry dust rag. The front plate can also be removed for
cleaning or exchange.
13 Technical data
Supply
Nominal Voltage 24 V DC
Tolerance +/-15%
Max interruption 20 ms
Recommended external fuse A20, B16, B20, S20, B22, D20, Pluto AS-i, O2: 6A
B46, S46, D45, B42 AS-i: 10A
Total current consumption A20, B16, B20, S20, B22, D20 Pluto AS-i: 5A max
B46, S46, D45, B42 AS-i: 7A max
O2: 1.3 A max
Own current consumption A20, B16, B20, S20, B22, D20 Pluto AS-i: 100…300 mA
B46, S46, D45, B42 AS-i: 100…500 mA
O2: 100 mA
Electrical installation: Category II according to IEC 61010-1
Failsafe inputs (including counter inputs)
I0, I1, I2, .. +24V (for PNP sensors)
IQ10, IQ11, .. +24V (for PNP sensors) also configurable as non-failsafe outputs.
Logic “1” > 12V
Logic “0” < 8V
Input current at 24V: 5.1 mA
Max. over voltage 27 V continuously
Analogue inputs (0-27V)
Range: 0…27 V
A20 family Terminal I5
Double family Terminal I5, I6 and I7
Pluto B42 AS-i Terminal I1, I2 and I3
Pluto AS-i Terminal I10, I11, I12 and I13
Analogue inputs (IA0-IA3, IA0-IA7)
Range: 0…10 V / 4...20mA
D20 Terminal IA0, IA1, IA2, IA3
D45 Terminal IA0, IA1, IA2, IA3, IA4, IA5, IA6, IA7
Resolution D20 10 bits
Resolution D45 12 bits
Accuracy D20 ±0.75% of full scale value
Accuracy D45
0 – 10V: ±0.4% of full scale value
4 – 20mA: ±0.2% of full scale value
Impedance D20
0 – 10V: >10 k
4 – 20mA: 420
Impedance D45
0 – 10V: >10k
4 – 20mA: 300
Counter inputs (Pluto D45)
Max frequency: 14 kHz at 50% duty cycle