EasyManua.ls Logo

ABB PSR - Page 24

ABB PSR
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cross section of connection cables
Type of softstarter
PSS18/30-500 ...
PSS44/76-500
PSS50/85-500 ...
PSS72/124-500,
PSS18/30-690 ...
PSS72/124-690
PSS85/147 ...
PSS142/245
PSS175/300 ...
PSS300/515
Main circuit
Connection clamp
Solid/stranded 1 x mm
2
2.5 – 16 6 – 50 See accessories
Solid/stranded 2 x mm
2
2.5 – 16 6 – 25 See accessories
Tightening torque
(recommended)
Nm 2.6 4.5 See accessories
Connection bar
Width and thickness mm
Hole diameter mm
Tightening torque
(recommended)
Nm
18 28
Supply and control circuit
Connection clamp
Solid/stranded 1 x mm
2
2.5 2.5 2.5
2.5
Solid/stranded 2 x mm
2
Tightening torque
(recommended)
Nm 0.5 0.5 0.5 0.5
E1858D
17.5
ø 8.5
5
E1859D
20
ø 10.2
5
24 Softstarters | 1SFC132005C0201, rev.F
PSS The flexible range
Technical data
Fuse ratings and power losses
Recommended
ABB Overload protection
Max power loss
at rated I
e
For
Softstarter
Current
range
without
by-pass
2)
with external
by-pass
Max fuse rating - main circuit
1) 3)
Power
requirements
of supply
Bussmann Fuses, DIN43 620 (Knife)
Type Type A W W A Type size VA
PSS18/30 TF42DU 7.6 - 18 65 13.5 50 170M1564 000 9
PSS30/52 TF42DU 7.6 - 30 100 14.6 80 170M1566 000 9
PSS37/64 TF42DU 7.6 - 37 120 17.5 125 170M1568 000 9
PSS44/76 TA75DU 18 - 44 142 17.5 160 170M1569 000 9
PSS50/85 TA75DU 18 - 50 160 20.5 160 170M1569 000 10
PSS60/105 TA75DU 18 - 60 190 22 200 170M1570 000 10
PSS72/124 TA75DU 18 - 72 226 30.5 250 170M1571 000 10
PSS85/147 TA110DU 65 - 85 291 56.5 315 170M1572 000 36
PSS105/181 TA110DU 65 - 105 351 61 400 170M3819 1* 36
PSS142/245 TA200DU 66 - 142 462 63 450 170M5809 2 36
PSS175/300 TA200DU 66 - 175 590 117 500 170M5810 2 65
PSS250/430 TA450DU 130 - 250 815 117 700 170M5813 2 65
PSS300/515 TA450DU 130 - 300 965 140 900 170M6813 3 65
1)
For the supply circuit 6 A delayed, for MCB use C characteristics.
2)
Calculated power loss at operational current (Iop) without by-pass.
Ptot = 3 x Iop + VA value
Example: PSS 60/105 running at 52A
Ptot = 3 x 52 + 10 = 166W
3)
Max fuse rating independent if In-Line or Inside Delta connection. In Inside Delta connections of PSS, the fuses can be placed outside of the delta.

Related product manuals