7:2.2 Application Setting
The Application setting menu consists of predened parameters for the selected applica-
tion and should be used if an easy and quick set-up is required. Only a few parameters
need to be set to allow the start of the motor. All necessary input data will show up in an
automatic loop.
Enter the Application setting
Enter the menu by selecting
Application Setting.
Select what type of application the softstarter is used for by pressing
Store Set. If the
desired application is not listed, select the one closest to the application and choose Tune
Set (see below). Possible applications are:
• Centrifugal Pump
• Hydraulic Pump
• Centrifugal Fan
• Axial Fan
• Compressor
• Conveyor
• Crusher
• Mixer
• Bow Thruster
Conrm the selected application by pressing Next. If the wrong application type was
selected, press Back and select the correct type.
Setting I
e
(motor FLA)
Set the motor full load current (i.e. rated motor current if the unit is connected In Line).
For units connected Inside Delta, the Setting I
e
must be set according to the current in the
delta circuit = 58% (1/( 3)) of the rated motor current.
Press Store to save the data after setting the current.
Conrm the Setting I
e
by pressing Next. If the wrong value is set, press Back and set the
correct value.
Overload class (OL Class)
Select the desired overload class. Available classes:
• 10A
• 10
• 20
• 30
Press Store to save the selected class.
Conrm the selected overload class by pressing
Next. If the wrong overload class was
selected, press Back and select the correct class.
External By-Pass contactor (Ext ByPass)
If an External Bypass contactor is used, set the parameter to Yes, otherwise select No.
Press Store to save the data.
Conrm the selection of external by-pass by pressing Next. If the wrong selection was
made, press Back and correct the selection.
Tune Set
The conguration of the application setting menu is now complete. If no tuning of the set-
tings is desired, it is possible to return to the top level by pressing Yes.
If tuning some parameters is desired, select Tune Set.
Figure 13: Conrming application type
Centrifugal Pump
Next Back
Figure 12: Application type
Centrifugal Pump
Store Set Back
Figure 11: Application setting menu
Application Setting
Select
Figure 20: Ready?/Tune Set menu
Figure 18: External By-Pass
Figure 17: Conrming OL Class
Figure 16: Overload class
Figure 15: Conrming Setting Ie
Figure 14: Setting Ie menu
Figure 10: Application setting menu
Top level
Settings
Application setting
Basic settings
Functional settings
Presentation settings
Service settings
All settings
Changed settings
Reset all settings
Operation mode
Chapter 7
Settings and conguration
Figure 19: Conrming External By-Pass
Low Voltage Products & Systems 7.9
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 021 M0201
7