7:2.2 Application Setting
The Application setting menu consists of predened parameters for the selected applica-
tion and should be used if an easy and quick set-up is required. Only a few parameters
need to be set to allow the start of the motor. All necessary input data will show up in an
automatic loop.
Enter the Application setting
Enter the menu by selecting
Application Setting.
Select what type of application the softstarter is used for by pressing
Store Set. If the
desired application is not listed, select the one closest to the application and choose Tune
Set (see below). Possible applications are:
Centrifugal Pump
Hydraulic Pump
Centrifugal Fan
Axial Fan
Compressor
Conveyor
Crusher
Mixer
Bow Thruster
Conrm the selected application by pressing Next. If the wrong application type was
selected, press Back and select the correct type.
Setting I
e
(motor FLA)
Set the motor full load current (i.e. rated motor current if the unit is connected In Line).
For units connected Inside Delta, the Setting I
e
must be set according to the current in the
delta circuit = 58% (1/( 3)) of the rated motor current.
Press Store to save the data after setting the current.
Conrm the Setting I
e
by pressing Next. If the wrong value is set, press Back and set the
correct value.
Overload class (OL Class)
Select the desired overload class. Available classes:
10A
10
20
30
Press Store to save the selected class.
Conrm the selected overload class by pressing
Next. If the wrong overload class was
selected, press Back and select the correct class.
External By-Pass contactor (Ext ByPass)
If an External Bypass contactor is used, set the parameter to Yes, otherwise select No.
Press Store to save the data.
Conrm the selection of external by-pass by pressing Next. If the wrong selection was
made, press Back and correct the selection.
Tune Set
The conguration of the application setting menu is now complete. If no tuning of the set-
tings is desired, it is possible to return to the top level by pressing Yes.
If tuning some parameters is desired, select Tune Set.
Figure 13: Conrming application type
Centrifugal Pump
Next Back
Figure 12: Application type
Centrifugal Pump
Store Set Back
Figure 11: Application setting menu
Application Setting
Select
Figure 20: Ready?/Tune Set menu
Ready?
Yes Tune Set
Figure 18: External By-Pass
Ext ByPass Yes
Store
Figure 17: Conrming OL Class
OL Class 10
Next Back
Figure 16: Overload class
OL Class 10
Store
Figure 15: Conrming Setting Ie
Setting Ie 100A
Next Back
Figure 14: Setting Ie menu
Setting Ie 100A
Store
Figure 10: Application setting menu
Top level
Settings
Application setting
Basic settings
Functional settings
Presentation settings
Service settings
All settings
Changed settings
Reset all settings
Operation mode
Chapter 7
Settings and conguration
Figure 19: Conrming External By-Pass
Ext ByPass Yes
Next Back