EasyManua.ls Logo

ABB PST210 - Low Current Warning; Overload Warning; SCR Overload Warning

ABB PST210
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 10
Functions
10:37 High current warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn I=High/Wa I=H Lev
This parameter makes it possible to set the indication level of the high current warning function.
Parameter text Default value Setting range Description
WA I=H Lev 1.2 x Ie 0.5...5.0 x Ie
Trip level for high cur-
rent warning
10:38 Low current warning
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn I=Low
If the function is selected, a warning signal will be given provided that the current during full
voltage is lower than the set value. The measurement starts 30 seconds after full voltage
is reached.
Parameter text Default value Setting range Description
WA I=Low No Yes, No Low current warning
10:39 Low current warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn I=Low/Wa I=L Lev
This parameter makes it possible to set the indication level of the low current warning function.
Parameter text Default value Setting range Description
WA I=L Lev 0.8 x Ie 0.4...1.0 x Ie
Trip level for low
current warning
10:40 Overload warning
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn OL
If the function is selected, a warning signal will be given that the overload protection will be
activated if the motor load does not decrease.
Parameter text Default value Setting range Description
Warn OL No Yes, No Overload warning
10:41 Overload warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn OL/Wa OL Lev
This parameter makes it possible to set the indication level of the motor overload protection.
The actual trip level of the protection is represented by 100%.
Parameter text Default value Setting range Description
Wa OL Lev 90% 40...99%
Trip level for overload
warning
10:42 SCR overload warning
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn SCR OL
If this function is selected, a warning signal will be given that the SCR overload protection
will be activated if the current does not decrease. The warning level is 90%.
Parameter text Default value Setting range Description
Warn SCR OL No Yes, No SCR overload warning
Low Voltage Products & Systems 10.11