Figure 23: Functional Settings menu
Top level
Settings
Application setting
Basic settings
Functional settings
Presentation settings
Service settings
All settings
Changed settings
Reset all settings
Operation mode
Seq. Start
Settings
Functional settings
Start / Stop
Protections
Warnings
Faults
Inputs
Outputs
Fieldbus
Figure 24: Start/Stop group
7:2.4 Functional Settings
The Functional setting menu consists of groups with parameters arranged by function
such as protection, warning, fault, eldbus communication etc. This menu should be
used if a more advanced set-up is required. For a detailed description of each param-
eter, see Chapter 10 “ Functions” .
Enter the Functional settings
Enter the menu by selecting Functional Settings.
7:2.4.1 Start/Stop
To set parameters related to start and stop, enter the Start/Stop group. The following
parameters are available in this group:
• Setting I
e
• External By-Pass
• Start ramp
• Stop ramp
• Initial voltage
• End voltage
• Step down voltage
• Current limit level
• Kick start
• Kick level
• Kick time
• Start range
• Stop range
To set parameters from Setting I
e
to Current limit level, see “Basic Settings”.
Kick Start
Activate the Kick Start function by entering this menu. Press Store to save the
selection.
Kick Level
Set the required level of the Kick Start. Press Store to save the data.
This menu will only be visible if Kick Start is activated.
Kick Time
Set the required time for the kick start. Press Store to save the data.
This menu will only be visible if Kick Start is activated.
Start Range
The ramp time for start can be set between 1 and 30 seconds as default. If required,
the range can be extended up to 120 seconds by entering this menu. Press Store to
save the data.
Stop Range
The ramp time for stop can be set between 0 and 30 seconds as default. If required,
the range can be extended up to 120 seconds by entering this menu. Press Store to
save the data.
The conguration of the parameters in the Start/Stop group is now completed. It is pos
-
sible to return to top level by pressing Back three times. To congure the protections,
proceed to that menu.