Underload
Activate the protection if required by changing to Yes.
If “Yes” is selected, the following settings will be available:
Underload level (
Underl Lev)
Set the level of the underload protection.
Available only if the protection is selected.
Underload time (Underl Time)
Set the time for the underload protection.
Available only if the protection is selected.
Underload type of operation (Underl Op)
Select what operation should be initiated if the underload protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press
Store to save the selected operation.
Phase imbalance (Phase Imb)
Activate the protection if required by changing to Yes.
If “Yes” is selected, the following settings will be available:
Phase imbalance level (Ph Imb Lev)
Set the level of the phase imbalance protection.
Available only if the protection is selected.
Phase imbalance type of operation (Ph Imb Op)
Select what operation should be initiated if the phase imbalance protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press
Store to save the selected operation.
High current (High I)
Activate the high current protection if required by changing to Yes.
If “Yes” is selected, the following setting will be available:
High current type of operation (High I Op)
Select what operation should be initiated if the high current protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and automatic reset is performed.
Ind Only indication will be given.
Press
Store to save the selected operation.
Phase reversal (Phase Rev)
Activate the phase reversal protection if required by changing to Yes. If “Yes” is selected,
the following setting will be available:
Phase reversal type of operation (Ph Rev Op)
Select what operation should be initiated if the phase reversal protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press
Store to save the selected operation.
PTC
Activate the PTC protection if required by changing to Yes.
If “Yes” is selected, the following setting will be available:
PTC type of operation (PTC Op)
Select what operation should be initiated if the PTC protection is activated:
Stop–M The motor will stop and a manual reset is required.
Stop–A The motor will stop and an automatic reset is performed.
Ind Only indication will be given.
Press
Store to save the selected operation.
Chapter 7
Settings and conguration
Low Voltage Products & Systems 7.13