7:2.4.5 Inputs
To set parameters related to the programmable inputs, enter the Inputs group.
First programmable input (In0)
Select the required function for the input In0.
Press Store to save/activate the selected function.
One of the following functions can be selected:
None No specic function (not activated).
Reset Reset of a fault or overload condition.
Enable When In0=0 the softstarter stops immediately.
When In0=1 the softstarter is in normal operation.
Overrides all other inputs except local control.
Jog Performs a start ramp until command is released. The motor stops
immediately when the input is opened.
DOL Open/close the bypass contactor (PSTB370...PSTB1050)
only if setting
Ie is equal to or lower than AC-3 rating.
Start2 Start signal for 2nd parameter set-up.
FB-Dis Disable the eldbus communication. The softstarter can be controlled
by hard wire inputs instead.
Press
Store to save/activate the selected function.
!
Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below:
• Switching from one type of controol to another (eldbus control/hardwire control)
• Re-programming the programmable inputs.
• Reset all Settings (programmable input set to Enable)
Second programmable input (In1)
Select the required function for the input In1.
One of the following functions can be selected:
None No specic function (not activated).
Reset Reset an event.
Enable When the In1=0 the softstarter stops immediately.
When In1=1 the softstarter is in normal operation.
Overrides all other inputs except local control.
Jog Performs a start ramp until command is released.
The motor stops immediately when the input opens.
DOL Open/close the bypass contactor (PSTB370...PSTB1050) only if setting Ie is
equal to or lower than AC-3 rating
.
Start3 Start signal for 3rd parameter set-up.
FB-Dis Disable the eldbus communication. The softstarter can be controlled by
hard-wire inputs instead.
Press
Store to save/activate the selected function.
!
Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below:
• Switching from one type of controol to another (eldbus control/hardwire control)
• Re-programming the programmable inputs.
• Reset all Settings (programmable input set to Enable)
Chapter 7
Settings and conguration
Figure 28: Inputs group
Seq. Start
Settings
Functional settings
Start / Stop
Protections
Warnings
Faults
Inputs
Outputs
Fieldbus