ABB PSTX Series - User Manual

ABB PSTX Series
258 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Softstarters Type PSTX30...PSTX1250
User Manual short form
1SFC132082M9901

Other manuals for ABB PSTX Series

Questions and Answers

  • D
    David WatersSep 10, 2025
    What does 'Phase reversal' mean on my ABB PSTX Controller?
    • E
      Emily WallaceSep 10, 2025
      Phase reversal indicates that the phase sequence is incorrect, leading to current imbalance between the phases. To correct this, change the phase sequence on the line side to (L1-L2-L3). Then, restart the motor and check the main currents and voltage.
  • O
    Omar HenrySep 8, 2025
    Why does my ABB PSTX motor make a bad sound during both start and stop?
    • C
      Crystal CookSep 8, 2025
      This could be due to several factors. First, try different settings for the Initial/End Voltage parameter. Also, experiment with different settings for the Current limit level or Torque limit level parameters. Ensure that you have the correct softstarter for the motor size. Make sure that the start and stop commands are not given at the same time. Check that the operation voltage is not below 175 V.
  • D
    Danielle NicholsSep 7, 2025
    What to do if loading parameters with Fieldbus does not work correctly on my ABB PSTX Controller?
    • C
      cclarkSep 7, 2025
      Ensure that the parameters match between the PLC and the Softstarter Fieldbus documentation for the used Fieldbus protocol. Make sure that the Auto mode bit of the binary output telegram setting is 1. Check if the HMI is set to remote control. Ensure that the Local Mode digital input on the ABB FieldBus Plug adapter is set to Remote. Make sure that Fieldbus disable control in DI is not connected. Verify that the Fieldbus control parameter is set to On.
  • L
    Lisa HaleAug 22, 2025
    What causes an electronic overload in my ABB PSTX and how can I resolve it?
    • J
      Jacqueline BurnsAug 23, 2025
      An electronic overload occurs when the motor current is too high for an extended period, often due to a high load on the motor shaft. To resolve this: * Examine start conditions and EOL settings. * Correct the reason for the overload. * Ensure the current limit level is not set too low. * Verify the ramp time for start is not too long. * Confirm the correct overload class is used. * Check that the Setting Ie parameter is correct.
  • C
    Chad EllisSep 4, 2025
    How do I fix an ABB PSTX that shows a blank screen and no LED is active?
    • E
      Elizabeth HallSep 4, 2025
      First, ensure that the supply voltage is properly connected, referring to the circuit diagram. Also check that the RJ45 plug is connected between the HMI and the softstarter, and that the RJ45 network cable is not damaged.
  • M
    markhendrixSep 3, 2025
    Why is my ABB PSTX showing a dark screen but the LED is active?
    • J
      Joshua WaltonSep 3, 2025
      The controller is likely in power save mode. Simply touch a key on the keypad to exit this mode.
  • S
    Sarah MosesSep 2, 2025
    What to do if my ABB PSTX motor is humming or starts without a given start signal?
    • R
      Regina FoxSep 2, 2025
      This issue could be due to a few reasons. If it's a PSTX30...170 model, a bypass relay might be closed due to inaccurate handling. To resolve this, disconnect the operation voltage and the control supply voltage, remove the USB cable if connected, and then reconnect the voltage in the following sequence: first, the control supply voltage on terminals 1 and 2 (refer to chapter 5.1.2), wait 4 seconds, and then connect the operation voltage on terminals L1, L2, and L3. Alternatively, the bypass contactor/relay could be stuck in a closed position, or there might be a shorted thyristor. In either of these cases, it is best to speak to your ABB Sales Office.
  • J
    Jason Barton DDSSep 1, 2025
    How to troubleshoot phase loss in ABB PSTX?
    • M
      Melanie WagnerSep 1, 2025
      Check that the mains are connected and that no line contactor or breaker is open. Inspect the fuses for all 3 phases, replacing any that are blown. Verify the operation network supply and correct it if there's a power loss on one or multiple phases. Ensure the contactor/breaker or external switch device is closed. If the line contactor opens too quickly at stop, control it with the Run signal relay on terminal 4, adding a time relay before the contactor opens. If Stop Ramp is not necessary, set Stop mode to direct stop.
  • R
    robertobonillaAug 30, 2025
    What to do if my ABB PSTX Controller motor does not start when given a start command by the hardwire inputs?
    • R
      robertbarberAug 31, 2025
      First, check the connections for start and stop. Make sure that the start and stop commands are not given at the same time. Ensure that the keypad is not in Local Control mode; if it is, push the R\L-key to change to Remote Control mode. Also, verify that the Fieldbus control parameter is set to No. Finally, reset any active or tripping events.
  • N
    Nathan SullivanAug 29, 2025
    What does 'Thyristor overload' mean on my ABB PSTX Controller?
    • S
      Sara BurnsAug 29, 2025
      A thyristor overload indicates that the thyristors are too hot. Check the start conditions and the fans. If possible, decrease the current limit. Allow the temperature of the thyristors to decrease before restarting.

Summary

1 Read this first

Safety Symbols and Information

Explains the meaning of warning, information, and graphical symbols used in the manual.

3 Mounting Instructions

Installation Requirements and Precautions

Covers drilling plans, enclosure size, clearances, air flow, HMI remote control, and general safety warnings.

4 Electrical Connection

Main Circuit Wiring and Safety

Details main circuit connections (line and motor side) and emphasizes hazardous voltage safety precautions.

4.1 Control and Signal Wiring

Control and Signal Wiring Details

Covers control supply, functional earth, start/stop circuits, and signal output relays connections.

4.2 Initial Power-up and Configuration

5 Human Machine Interface (HMI)

6 Softstarter Settings and Configuration

Initial Setup Assistant and Menu Navigation

Guides through the first start-up assistant and navigating the assistants menu for initial configuration.

Parameter Configuration Guidance

Explains how to configure motor rated current based on connection type (In Line or Inside Delta).

6.1 HMI Navigation and Parameter Access

HMI Navigation Methods

Explains HMI navigation methods (menu, numerical, on/off, selection) for setting parameters.

6.2 Options Settings and Safety

7 Troubleshooting and Fault Events

Event List and Fault Descriptions

Lists and describes common softstarter events and fault conditions like overload, phase loss, and voltage issues.

7.1 Fault Conditions

Fault Conditions and Causes

Details fault causes such as high current, phase loss, heat sink overtemperature, network quality, and thyristor issues.

7.2 Warning Conditions

Warning Conditions and Actions

Explains warning conditions like current underload, voltage imbalance, and limits for starts/run time.

Electrical Connections Details

Wiring and Connection Bars per Model

Specifies wiring methods, connection bar types, torque values, and cable sizes for different PSTX models.

Control Circuit Wiring Diagrams

Circuit Diagrams

HMI Parameter Settings

ABB PSTX Series Specifications

General IconGeneral
TypeSoftstarter
Rated operational voltage208-690 V AC
Rated operational current30-1250 A
Number of phases3
Operating temperature-25 to +60°C
Operating frequency50/60 Hz
Overload protectionYes
Protection classIP20
Communication protocolsModbus RTU, Profibus
Starting methodVoltage ramp, current limit
Stopping methodsoft stop
Bypass contactorBuilt-in
Displaygraphical display
Rated control supply voltage100-240V AC