ABB RED670 - Page 257

ABB RED670
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 39: Activate input signals if OpMode = 2 Out Of 2
INPut
CR1 X X X X X X
CHERR1 X
CR2 X X X X X
CHERR2 X
LOCTR X X X
LOCTRL1 X
LOCTRL2 X
LOCTRL3 X
Table 40: Activate output signals if OpMode = 2 Out Of 2
OUTPut
Non X X
TRIP X X X X X
TRL1 X
TRL2 X
TRL3 X
7. Connect the trip output to a timer.
8. Have inputs CR1and CR2 activated. Start the timer from activation of input
LOCTR and stop the timer from TRIP output.
9. Check the trip time.
If OpMode = 1 Out Of 2:
10. Activate input and check output signals according to table 41 and 42.
Table 41: Activate input signals if OpMode = 1 Out Of 2
INPut
CR1 X X X X X
CHERR1 X
CR2 X X X X X X
CHERR2
LOCTR X X X
LOCTRL1 X X
LOCTRL2 X X
LOCTRL3 X X
1MRK 505 378-UEN A Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC 251
Commissioning manual