IEC140000142 V1 EN-US
Figure 14: Start capturing the IEEE C37.118 synchrophasor data
• The synchrophasor data capturing process can be stopped at any point of time
by navigating to File/Capture/Stop Stream Debug Capture...
1MRK 505 378-UEN A Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Line differential protection RED670 2.2 IEC 83
Commissioning manual