Line description: Channel descriptor”“Channel number : Values
Channel descriptor: Analog input
Channel number: x, where x addresses the analog input channel.
Values: CT (1-5 A) Rated secondary current related to the current input.
CT (0,2 A) Rated secondary current.
VT (100 V) Rated secondary voltage (Volt).
Sensor Voltage output of the sensor (Volt).
A051356
Fig. 14.3.-1 Analog inputs commissioning page for the 3CT, 3VT, 1VT, 1CT module
With sensor inputs, the displayed values are the voltages read by the analog
channels. For example, by using the voltage divider 10.000/1 applying 20 kV on the
sensor, the measurement will show 2 Volt. For the current sensor 80 A/150 mV,
applying 80 Amp on the sensor the measure will be 0.150 Volt.
Multifunction Protection and Switchgear Control Unit
Operator's manual
REF 542plusREF 542plus