SESRSYN CBConfig
setting
Section to
be
synchroniz
ed
Activated
B1QCLD
input on
IED from
Activated
B2QCLD
input on
IED from
Activated
LN1QCLD
input on
IED from
Activated
LN2QCLD
input on
IED from
Indication
from
SESRSYN
on IED
SESRSYN 3
(Operates on
CB3QA1)
1 ½ bus
alt. CB
(mirrored)
Bus2 –
Line2
LN2QB9 B2SEL,
LN2SEL
Bus2 –
Line1
CB2QA1 LN1QB9 B2SEL,
LN1SEL
Bus2 –
Bus1
CB2QA1 CB1QA1 B1SEL,
B2SEL
Bus 1
Bus 2
CB1QA1
(SESRSYN 1)
CB3QA1
(SESRSYN 3)
CB2QA1
(SESRSYN 2)
Line 1 Line 2
LN1QB9 LN2QB9
IEC11000274-2-en.vsd
IEC11000274 V2 EN
Figure 21: Objects used in the voltage selection logic
Testing the voltage difference
Set the voltage difference to 0.15 p.u. on the local HMI, and the test should check that
operation is achieved when the voltage difference UDiffSC is lower than 0.15 p.u.
The settings used in the test shall be final settings. The test shall be adapted to site
setting values instead of values in the example below.
Test with no voltage difference between the inputs.
Test with a voltage difference higher than the set UDiffSC.
Section 6 1MRK 502 049-UEN A
Testing functionality
102
Commissioning manual