Section 4 1MRS240173-IB B
1x Registers
22 REF615R
DPU2000R Modbus Point List Mitigation Manual
10002 Breaker Status (52a = 0 52b= 1 CB Open)
(52b)
10002 CTRL.CBCSWI1.PosOpn.stVal Apparatus open position
10003 Enable Reclose Function Asserted (43a) 10003 *LD0.DARREC1.AROn.stVal Auto reclosing allowed
10004 Enable Phase Over current Protection for all
Phase elements except 50P-3 (PH3)
See Section 7.2.1 for
example or explanation
10005 Enable Ground Over current Protection for all
Ground elements except 50N-3 (GRD)
See Section 7.2.2 for
example or explanation
10006 Spring Charging Contact Function Enabled
(SCC)
10006 LD0.SSCBR1.InSprCha.stVal
10007 Single Shot Reclosing Enabled (79S) N/A in REF615R
10008 Multiple Shot Reclosing Enabled (79M) 10008 LD0.DARREC1.InReClsOn.stVal
10009 Trip Coil Monitoring Enabled (TCM) N/A in REF615R
10010 Enable 50P-1 and 50N-1 (50-1) See Section 7.2.3 for
example or explanation
10011 Enable 50P-2 and 50N-2 (50-2) See Section 7.2.4 for
example or explanation
10012 Enable 50P-3 and 50N-3 (50-3) See Section 7.2.5 for
example or explanation
10013 Enable Alternate 1 Settings (ALT1) See Section 7.2.6 for
example or explanation
10014 Enable Alternate 2 Settings (ALT2) See Section 7.2.7 for
example or explanation
10015 Initiate Event Capture 1 (ECI1) N/A in REF615R
10016 Initiate Event Capture 2 (ECI2) N/A in REF615R
10017 Waveform Capture Initiate (WCI) DR.RDRE1.RcdTrg.stVal
10018 Enable Zone Sequence Coordination (ZSC) 10018 LD0.DARREC1.ProCrd.stVal
10019 Initiate Trip Output (OPEN) 10019 CTRL.CBCSWI1.OpOpn.general
10020 Initiate Close Output (CLOSE) 10020 CTRL.CBCSWI1.OpCls.general
10021 Enable Negative Sequence Time Over current
Function (46)
10021 LD0.NSPTOC1.Mod.blockIn
10022 Enable Positive Sequence Directionally
Controlled Phase Time Over current Function
(67P-1)
N/A in REF615R
10023 Enable Negative Sequence Directionally
Controlled Phase Time Over current Function
(67N)
N/A in REF615R
10024 User Logical Input 1 Element Energized (ULI1) N/A in REF615R
10025 User Logical Input 2 Element Energized (ULI2) N/A in REF615R
10026 User Logical Input 3 Element Energized (ULI3) N/A in REF615R
10027 User Logical Input 4 Element Energized (ULI4) N/A in REF615R
10028 User Logical Input 5 Element Energized (ULI5) N/A in REF615R
10029 User Logical Input 6 Element Energized (ULI6) N/A in REF615R
10030 User Logical Input 7 Element Energized (ULI7) N/A in REF615R
10031 User Logical Input 8 Element Energized (ULI8) N/A in REF615R
10032 User Logical Input 9 Element Energized (ULI9) N/A in REF615R
DPU2000R
register
addr.
DPU 2000R description
REF615R
register
addr.
IEC 61850 path
Comments on REF615R
Modbus points mapping