1MRS240173-IB B Section 5
4x Registers
REF615R 47
DPU2000R Modbus Point List Mitigation Manual
5.3.2 Operation records
REF615R substitutes Modbus events for the operation records in DPU2000R
41435 KVab/ KVan (Mag) 100 41435 100 LD0.FLTMSTA1.VoltsAB.mag.f KVab in per unit
41453 100 LD0.FLTMSTA1.VoltsA.mag.f KVan in per unit
41436 KVbc / KVbn (Mag) 100 41436 100 LD0.FLTMSTA1.VoltsBC.mag.f KVbc in per unit
41454 100 LD0.FLTMSTA1.VoltsB.mag.f KVbn in per unit
41437 KVca / KVcn (Mag) 100 41437 100 LD0.FLTMSTA1.VoltsCA.mag.f KVca in per unit
41455 100 LD0.FLTMSTA1.VoltsC.mag.f KVcn in per unit
41438 Vab / Van (Ang) 1 N/A in REF615R
41439 Vbc / Vbn (Ang) 1 N/A in REF615R
41440 Vca / Vcn (Ang) 1 N/A in REF615R
41441 Pos Seq KV (Mag) 100 41441 100 LD0.FLTMSTA1.VPsSeq.mag.f in per unit
41442 Neg Seq KV (Mag) 100 41442 100 LD0.FLTMSTA1.VNgSeq.mag.f in per unit
41443 Pos Seq V (Ang) 1 N/A in REF615R
41444 Neg Seq V (Ang) 1 N/A in REF615R
41445 Fault Location 10 41445 LD0.FLTMSTA1.FltDisKm.mag.f Distance to fault measured in
pu
41446-41447 fault impedance,
real
1000 41446-
41448
1000 LD0.FLTMSTA1.FltZ.cVal.mag.f 41446-41447 mapped for
impedance magnitude, 41448
mapped for angle.
41448-41449 breaker operate
time
1000 41449-
41450
1000 LD0.FLTMSTA1.OpTm.mag.f
41450-41451 Relay operate time 1000 N/A in REF615R
41452 Record status 41452 Record status
DPU2000R
register addr.
DPU 2000R
description
Scale
REF615R
register
addr.
Scale IEC 61850 path
Comments on REF615R
Modbus points mapping
REF615R Modbus protocol only reads the fault records generated after the
device powers up.WebHMI can be used to read entire set of fault records
saved in the relay.
To find out the entire set of fault records in REF615R, please check
"Feeder Protection and Control REF615R Modbus Point List Manual" with
Document ID: 1MRS240052-IB.
REF615R Modbus server only provides Modbus events generated after the
device powers up. WebHMI or ftp tool can be used to upload a complete
set of event records stored in the flash memory.