EasyManua.ls Logo

ABB Relion REF615R - Function Code 23 (Read;Write 4 X Registers); Fault Record

ABB Relion REF615R
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MRS240173-IB B Section 5
4x Registers
REF615R 45
DPU2000R Modbus Point List Mitigation Manual
Totally there are 15 control blocks in REF615R. Please check "REF615R Modbus
Communication Protocol Manual", Document ID: 1MRS240047-IB, section 3.3.6 for
more details on how to use control blocks. REF615R has added several control commands
which are not available in DPU2000R. To find out entire REF615R control commands,
please check "Feeder Protection and Control REF615R Modbus Point List Manual"
document ID: 1MRS240052-IB, the table of Control Structures.
5.3 Function code 23 (Read/write 4x registers)
5.3.1 Fault Record
REF615R maps the fault records format and contents as close as possible to those in
DPU2000R.
41201:6 OUT5 41207:8 LD0.XUGGIO100.SPCSO5.Oper.ctlVal Normal speed BIO card, need to set relay in
test mode and remote mode
41212:8 LD0.XBUGGIO100.SPCSO5.Oper.ctlVal High speed BIO card, need to set relay in
test mode and remote mode
41201:5 OUT4 41207:6 LD0.XUGGIO100.SPCSO4.Oper.ctlVal Normal speed BIO card, need to set relay in
test mode and remote mode
41212:6 LD0.XBUGGIO100.SPCSO4.Oper.ctlVal High speed BIO card, need to set relay in
test mode and remote mode
41201:4 OUT3 41207:4 LD0.XUGGIO100.SPCSO3.Oper.ctlVal Normal speed BIO card, need to set relay in
test mode and remote mode
41212:4 LD0.XBUGGIO100.SPCSO3.Oper.ctlVal High speed BIO card, need to set relay in
test mode and remote mode
41201:3 OUT2 41207:2 LD0.XUGGIO110.SPCSO2.Oper.ctlVal Normal speed BIO card, need to set relay in
test mode and remote mode
41212:2 LD0.XBUGGIO110.SPCSO2.Oper.ctlVal High speed BIO card, need to set relay in
test mode and remote mode
41201:2 OUT1 41207:0 LD0.XUGGIO110.SPCSO1.Oper.ctlVal Normal speed BIO card, need to set relay in
test mode and remote mode
41212:0 LD0.XBUGGIO110.SPCSO1.Oper.ctlVal High speed BIO card, need to set relay in
test mode and remote mode
41201:1 Close(reserved)
41201:0 Trip 41207:12 LD0.XUGGIO100.SPCSO1.Oper.ctlVal Normal speed BIO card, need to set relay in
test mode and remote mode
41212:12 LD0.XBUGGIO100.SPCSO1.Oper.ctlVal High speed BIO card, need to set relay in
test mode and remote mode
DPU2000R
register
addr.
DPU 2000R
description
REF615R
register
addr.
IEC 61850 path
Comments on REF615R Modbus points
mapping
Modbus client controlling physical contacts only works when the
REF615R protection relay is set at both remote and test mode.

Table of Contents