Section 5 1MRS240173-IB B
4x Registers
44 REF615R
DPU2000R Modbus Point List Mitigation Manual
41159:1 Close Initiate
(Based on 43a)
N/A in REF615R
41159:0 Trip Initiate 41157:0 CTRL.CBCSWI1.Pos.Oper.ctlVal
“Open” command in
SBO-with-enhanced-security
mode.
(Relay needs to be set at Remote
mode at first).
41157:2 “Cancel” command in
SBO-with-enhanced-security mode. Send
this command within 15 seconds delay after
sending the “Open” command to cancel
execute the “Open” command.
41157:3 “Select” command in
SBO-with-enhanced-security mode. Send
this command within 15 seconds delay after
sending the “Open” command to confirm
execute the “Open” command.
41157:4
“Open” command in
direct-with-normal-security mode.
(Relay needs to be set at Remote mode at
first).
41160-411
66
Force physical
input
N/A in REF615R
41167-411
73
Force physical
output
Check momentary output contact controls in
test mode
41174-411
83
Force logical
input command
N/A in REF615R
41184-411
95
Set/Reset
command
registers
41214-41
223
LD0.SRGAPC1-2.Rs1-8.Oper.ctlVal and
LD0.SRGAPC3-4.Rs1-8.Oper.ctlVal
Totally 2 blocks of set reset control
commands. Each block has 16 control
points.
41189 ULOx controls N/A in REF615R
41196 Execute on
momentary
output contact
registers
Password 2 for control structure 9.
41197 Password
character 1 & 2
41197:0-
15
LD0.SPCRGGIO1.SPCSO(1to8).Oper.ctlVal
This address is mapped for different points
in REF615R than in DPU2000R.
41198 Password
character 3 & 4
41198 Confirmation register for control block 9.
41199 Spare 41199 Execute register for control bock 10.
41200 Momentary
output contact
state mask
41200 Password 1 for control block 10.
41201 Confirmation
momentary
output contact
state mask
41201 Password 2 for control block 10.
41201:7 OUT6 41207:10 LD0.XUGGIO100.SPCSO6.Oper.ctlVal Normal speed BIO card, need to set relay in
test mode and remote mode
41212:10 LD0.XBUGGIO100.SPCSO6.Oper.ctlVal High speed BIO card, need to set relay in
test mode and remote mode
DPU2000R
register
addr.
DPU 2000R
description
REF615R
register
addr.
IEC 61850 path
Comments on REF615R Modbus points