1MRS240173-IB B Section 5
4x Registers
REF615R 41
DPU2000R Modbus Point List Mitigation Manual
5.1.8 Physical and Logical Input / Output state Block
REF615R maps the 4x registers with packed bits in the same address locations as in
DPU2000R. The table 17 gives an example of packed bits in 40897.
Table 17: Mitigation of Modbus physical and logical input/output state block
40772 Sum of fault current B 1 Read addr. 42012 for
reference.
40773 sum of fault current C 1 Read addr. 42014 for
reference.
40774 Over current trip counter 1 See Section Section 7 for
example or explanation
40775 breaker operations counter 1 40775 1 LD0.SSCBR1.OpCnt.stVal
40776 Recloser Counter 1 1 40776 1 LD0.DARREC1.FrqOpCnt.stVal
40777 Recloser Counter 2 1 40777 1 N/A in REF615R
40778 State 1 Reclose Counter 1 40778 1 LD0.DARREC1.OpCnt1.stVal
40779 State 2 Reclose Counter 1 40779 1 LD0.DARREC1.OpCnt2.stVal
40780 State 3 Reclose Counter 1 40780 1 LD0.DARREC1.OpCnt3.stVal
40781 State 4 Reclose Counter 1 40781 1 LD0.DARREC1.OpCnt4.stVal
40782 State 5 Reclose Counter 1 40782 1 LD0.DARREC1.OpCnt5.stVal
40771 Sum of fault current A 1 42010 100 LD0.SSCBR1.AccAPwrPhA.mag.f Can be used for Sum of fault
current A
40772 Sum of fault current B 1 42012 100 LD0.SSCBR1.AccAPwrPhB.mag.f Can be used for Sum of fault
current B
40773 Sum of fault current C 1 42014 100 LD0.SSCBR1.AccAPwrPhC.mag.f Can be used for Sum of fault
current C
DPU2000R
register
addr.
DPU2000R description Scale
REF615R
register
addr.
Scale IEC61850 path
Comments on REF615R
Modbus points mapping
DPU2000R
register
addr.
DPU 2000R description
REF615R
register
addr.
IEC 61850 path Comments on REF615R Modbus points mapping
40897:15 Breaker is Tripping (TRIP ) 40897:15 LD0.TRPPTRC1.Tr.general
40897:14 Breaker is Closing (Close ) 40897:14 LD0.MVGAPC8.Q3.stVal Configured by PCM600 tool.
40897:13 DPU is in ALARM (ALARM) 40897:13 LD0.LLN0.Health.stVal Converted enum value to boolean to read
ALARM status
40897:12 Under voltage Trip
(27-1P )
40897:12 LD0.PHPTUV1.Op.general
40897:11 Negative Sequence
Over-current Trip (46)
40897:11 LD0.NSPTOC1.Op.general
40897:10 Phase Instantaneous
Over-current Trip (50P1)
40897:10 LD0.PHHPTOC1.Op.general
40897:9 Neutral Instantaneous
Over-current Trip (50N1 )
40897:9 LD0.EFHPTOC3.Op.general
40897:8 Phase Instantaneous
Over-current Trip (50P2)
40897:8 LD0.PHHPTOC2.Op.general
40897:7 Neutral Instantaneous
Over-current Trip (50N2 )
40897:7 LD0.EFHPTOC4.Op.general