1MRS240173-IB B Section 5
4x Registers
REF615R 39
DPU2000R Modbus Point List Mitigation Manual
Table 15: Mitigation of Modbus mappings for minimum demand current/real, reactive power values and time
stamps block
DPU2000R
register
addr.
DPU2000R description Scale
REF615R
register
addr.
Scale IEC61850 path
Comments on
REF615R
Modbus points
mapping
40641 Minimum Demand Current-A 1 40641 100 LD0.CMSTA1.MinAmpsA.mag.f reading per unit
value by default
40642 Minimum Demand Current-A Year,
Month
40642 LD0.CMSTA1.MinAmpsA.t Year, Month
40643 Minimum Demand Current-A Day,
Hour
40643 Day, Hour
40644 Minimum Demand Current-A Minute 40644 Minute
40645 Minimum Demand Current-B 1 40645 100 LD0.CMSTA1.MinAmpsB.mag.f reading per unit
value by default
40646 Minimum Demand Current-B Year,
Month
40646 LD0.CMSTA1.MinAmpsB.t Year, Month
40647 Minimum Demand Current-B Day,
Hour
40647 Day, Hour
40648 Minimum Demand Current-B Minute 40648 Minute
40649 Minimum Demand Current-C 1 40649 100 LD0.CMSTA1.MinAmpsC.mag.f reading per unit
value by default
40650 Minimum Demand Current-C Year,
Month
40650 LD0.CMSTA1.MinAmpsC.t Year, Month
40651 Minimum Demand Current-C Day,
Hour
40651 Day, Hour
40652 Minimum Demand Current-C Minute 40652 Minute
40653 Minimum Demand Current-N 1 40653 100 LD0.RESCMSTA1.MinAmps.mag.f reading per unit
value by default
40654 Minimum Demand Current-N Year,
Month
40654 LD0.RESCMSTA1.MinAmps.t Year, Month
40655 Minimum Demand Current-N Day,
Hour
40655 Day, Hour
40656 Minimum Demand Current-N Minute 40656 Minute
40657 Minimum Demand KWatts-A 1 40657 1 LD0.SPEMSTA1.MinWPhsA.mag.f
40659 Minimum Demand KWatts-A Year,
Month
40659 LD0.SPEMSTA1.MinWPhsA.t Year, Month
40660 Minimum Demand KWatts-A Day,
Hour
40660 Day, Hour
40661 Minimum Demand KWatts-A Minute 40661 Minute
40662 Minimum Demand KWatts-B 1 40662 1 LD0.SPEMSTA1.MinWPhsB.mag.f
40664 Minimum Demand KWatts-B Year,
Month
40664 LD0.SPEMSTA1.MinWPhsB.t Year, Month
40665 Minimum Demand KWatts-B Day,
Hour
40665 Day, Hour
40666 Minimum Demand KWatts-B Minute 40666 Minute
40667 Minimum Demand KWatts-C 1 40667 1 LD0.SPEMSTA1.MinWPhsC.mag.f
40669 Minimum Demand KWatts-C Year,
Month
40669 LD0.SPEMSTA1.MinWPhsC.t Year, Month
40670 Minimum Demand KWatts-C Day,
Hour