EasyManua.ls Logo

ABB Relion REF615R - Table 15. Mitigation of Modbus Mappings for Minimum Demand Current;Real, Reactive Power Values and Time Stamps Block

ABB Relion REF615R
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MRS240173-IB B Section 5
4x Registers
REF615R 39
DPU2000R Modbus Point List Mitigation Manual
Table 15: Mitigation of Modbus mappings for minimum demand current/real, reactive power values and time
stamps block
DPU2000R
register
addr.
DPU2000R description Scale
REF615R
register
addr.
Scale IEC61850 path
Comments on
REF615R
Modbus points
mapping
40641 Minimum Demand Current-A 1 40641 100 LD0.CMSTA1.MinAmpsA.mag.f reading per unit
value by default
40642 Minimum Demand Current-A Year,
Month
40642 LD0.CMSTA1.MinAmpsA.t Year, Month
40643 Minimum Demand Current-A Day,
Hour
40643 Day, Hour
40644 Minimum Demand Current-A Minute 40644 Minute
40645 Minimum Demand Current-B 1 40645 100 LD0.CMSTA1.MinAmpsB.mag.f reading per unit
value by default
40646 Minimum Demand Current-B Year,
Month
40646 LD0.CMSTA1.MinAmpsB.t Year, Month
40647 Minimum Demand Current-B Day,
Hour
40647 Day, Hour
40648 Minimum Demand Current-B Minute 40648 Minute
40649 Minimum Demand Current-C 1 40649 100 LD0.CMSTA1.MinAmpsC.mag.f reading per unit
value by default
40650 Minimum Demand Current-C Year,
Month
40650 LD0.CMSTA1.MinAmpsC.t Year, Month
40651 Minimum Demand Current-C Day,
Hour
40651 Day, Hour
40652 Minimum Demand Current-C Minute 40652 Minute
40653 Minimum Demand Current-N 1 40653 100 LD0.RESCMSTA1.MinAmps.mag.f reading per unit
value by default
40654 Minimum Demand Current-N Year,
Month
40654 LD0.RESCMSTA1.MinAmps.t Year, Month
40655 Minimum Demand Current-N Day,
Hour
40655 Day, Hour
40656 Minimum Demand Current-N Minute 40656 Minute
40657 Minimum Demand KWatts-A 1 40657 1 LD0.SPEMSTA1.MinWPhsA.mag.f
40659 Minimum Demand KWatts-A Year,
Month
40659 LD0.SPEMSTA1.MinWPhsA.t Year, Month
40660 Minimum Demand KWatts-A Day,
Hour
40660 Day, Hour
40661 Minimum Demand KWatts-A Minute 40661 Minute
40662 Minimum Demand KWatts-B 1 40662 1 LD0.SPEMSTA1.MinWPhsB.mag.f
40664 Minimum Demand KWatts-B Year,
Month
40664 LD0.SPEMSTA1.MinWPhsB.t Year, Month
40665 Minimum Demand KWatts-B Day,
Hour
40665 Day, Hour
40666 Minimum Demand KWatts-B Minute 40666 Minute
40667 Minimum Demand KWatts-C 1 40667 1 LD0.SPEMSTA1.MinWPhsC.mag.f
40669 Minimum Demand KWatts-C Year,
Month
40669 LD0.SPEMSTA1.MinWPhsC.t Year, Month
40670 Minimum Demand KWatts-C Day,
Hour
40670 Day, Hour

Table of Contents