EasyManua.ls Logo

ABB REM 610 - Checking the Need for Speed Switch; Start-Up Supervision; Start-Up Supervision Based on Thermal Stress Calculation; Time Constant Dial, Kc

ABB REM 610
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Generally, the prior alarm level is set to 8090 per cent of the trip level.
6.1.2.7. Time constant dial, K
c
The time constant dial, K
c
, is the ratio of the cooling time (at motor standstill) and
the heating time constant:
K
cooling
heating
c
=
τ
τ
(10)
Generally, the time constant dial of the motor is set to 4...6. However, when
protecting non-rotating objects, e.g. feeder cables or transformers, for instance, the
time constant dial is generally set to one.
6.1.3. Start-up supervision
Start-up supervision is based on thermal stress calculation by default but can also be
set to be based on definite-time overcurrent protection, especially in other than
motor applications.
6.1.3.1. Start-up supervision based on thermal stress calculation
The start-up current, 48/14 PICKUP, is set to equal the start-up current of the motor
and the start-up time, 48/14 TDLY, to approximately ten per cent above the start-up
time of the motor in order to leave a safety margin for operation.
For instance, if the start-up current of the motor is 6.2 x FLA and the start-up time
11 seconds, 48/14 PICKUP = 6.2 and 48/14 TDLY = 11 s x 1.1 = 12 s.
6.1.3.2. Checking the need for speed switch
When protecting motors of ExE-type, for instance, the safe stall time may be shorter
than the start-up time of the motor, which is why a speed switch on the motor shaft
is required to give information on whether the motor is accelerating during motor
start up. In this case, the start-up time is set to slightly below the safe stall time.
The speed switch should be open at standstill and closed during acceleration. When
the input is activated, element (48/14 PICKUP)
2
x (48/14 TDLY)/(48/14) will be
blocked. If the motor does not start to accelerate, element (48/14 PICKUP)
2
x (48/
14 TDLY) will trip when the reference value, (48/14 PICKUP)
2
x (48/14 TDLY), is
exceeded. If start-up supervision is based on overcurrent protection, element 48/14
will trip on expiration of the set operate time
However, if the safe stall time is longer than the start-up time of the motor when no
prior load, a speed switch will not be required.
134
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537

Table of Contents

Other manuals for ABB REM 610

Related product manuals