8. Check lists
Table 8.-1 Setting group 1
Variable Group/
Channel 1
(R, W, P)
Setting range Default
setting
Customer’s
setting
Safe stall time 1S1 2...120 s 2 s
Weighting factor 1S2 20...100% 50 %
Time constant dial 1S3 1...64 1
Prior alarm level 1S4 50...100% 95 %
Restart disable level 1S5 20...80% 40 %
Ambient temperature 1S6 0...70°C 40°C
Start-up current for motor or
pickup value of element 48/
14
1S7 1.00…10.0 x FLA 1.00 x FLA
Start-up time for motor or
operate time of element 48/
14
1S8 0.30...80.0 s 0.30 s
Pickup value of element 50P 1S9 0.50...20.0 x FLA 1.00 x FLA
Operate time of element 50P 1S10 0.05...30.0 s 0.05 s
Pickup value of element 51N 1S11 1.0...100% I
n
CT 1.0% I
n
CT
Operate time of element 51N 1S12 0.05...300 s 0.05 s
Pickup value of element 37 1S13 30...80% FLA 50% FLA
Operate time of element 37 1S14 2...600 s 2 s
Pickup value of element 46 1S15 0.10…0.50 x FLA 0.20 x FLA
Time constant of element 46
at IDMT characteristic
1S16 5...100 5
Restart disable value 1S17 5...500 s 5 s
Countdown rate of start-up
time counter
1S18 2...250 s/h 2 s/h
Operate time of CBFAIL 1S19 0.10...60.0 s 0.10 s
Alarm value RTD1A 1S20 0...200°C 0°C
Operate time RTD1A TDLY 1S26 1...100 s 1 s
Trip value RTD1T 1S32 0...200°C 0°C
Operate time RTD1T TDLY 1S38 1...100 s 1 s
Alarm value RTD2A 1S21 0...200°C 0°C
Operate time RTD2A TDLY 1S27 1...100 s 1 s
Trip value RTD2T 1S33 0...200°C 0°C
Operate time RTD2T TDLY 1S39 1...100 s 1 s
Alarm value RTD3A 1S22 0...200°C 0°C
Operate time RTD3A TDLY 1S28 1...100 s 1 s
Trip value RTD3T 1S34 0...200°C 0°C
Operate time RTD3T TDLY 1S40 1...100 s 1 s
Alarm value RTD4A 1S23 0...200°C 0°C
Operate time RTD4A TDLY 1S29 1...100 s 1 s
Trip value RTD4T 1S35 0...200°C 0°C
Operate time RTD4T TDLY 1S41 1...100 s 1 s
Alarm value RTD5A 1S24 0...200°C 0°C
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610REM 610
1MRS755537