Variable Group/
Channel 1
(R, W, P)
Setting range Default
setting
Customers
setting
Operate time RTD5A TDLY 1S30 1...100 s 1 s
Trip value RTD5T 1S36 0...200°C 0°C
Operate time RTD5T TDLY 1S42 1...100 s 1 s
Alarm value RTD6A 1S25 0...200°C 0°C
Operate time RTD6A TDLY 1S31 1...100 s 1 s
Trip value RTD6T 1S37 0...200°C 0°C
Operate time RTD6T TDLY 1S43 1...100 s 1 s
Trip value PTC1 1S44 0.1...15.0 kΩ 0.1 kΩ
Trip value PTC2 1S45 0.1...15.0 kΩ 0.1 kΩ
Checksum, SGF 1 1S61 0...255 0
Checksum, SGF 2 1S62 0...255 0
Checksum, SGF 3 1S63 0...255 2
Checksum, SGF 4 1S64 0...7 0
Checksum, SGF 5 1S65 0...255 0
Checksum, SGB 1 1S71 0...16383 0
Checksum, SGB 2 1S72 0...16383 0
Checksum, SGB 3 1S73 0...16383 0
Checksum, SGB 4 1S74 0...16383 0
Checksum, SGB 5 1S75 0...16383 0
Checksum, SGR 1 1S81 0...524287 6826
Checksum, SGR 2 1S82 0...524287 6826
Checksum, SGR 3 1S83 0...524287 0
Checksum, SGR 4 1S84 0...524287 9557
Checksum, SGR 5 1S85 0...524287 9557
Checksum, SGL 1 1S91 0...4194303 4
Checksum, SGL 2 1S92 0...4194303 8
Checksum, SGL 3 1S93 0...4194303 0
Checksum, SGL 4 1S94 0...4194303 0
Checksum, SGL 5 1S95 0...4194303 0
Checksum, SGL 6 1S96 0...4194303 0
Checksum, SGL 7 1S97 0...4194303 0
Checksum, SGL 8 1S98 0...4194303 0
Table 8.-2 Setting group 2
Variable Group/
Channel 2
(R, W, P)
Setting range Default
setting
Customers
setting
Safe stall time 2S1 2...120 s 2 s
Weighting factor 2S2 20...100% 50 %
Time constant dial 2S3 1...64 1
Prior alarm level 2S4 50...100% 95 %
Restart disable level 2S5 20...80% 40 %
Ambient temperature 2S6 0...70°C 40°C