149
Variable Group/
Channel 2
(R, W, P)
Setting range Default
setting
Customer’s
setting
Start-up current for motor or
start value of element 48/14
2S7 1.00…10.0 x FLA 1.00 x FLA
Start-up time for motor or
operate time of element 48/
14
2S8 0.30...80.0 s 0.30 s
Pickup value of element 50P 2S9 0.50...20.0 x FLA 1.00 x FLA
Operate time of element 50P 2S10 0.05...30.0 s 0.05 s
Pickup value of element 51N 2S11 1.0...100% I
n
CT 1.0% I
n
CT
Operate time of element 51N 2S12 0.05...300 s 0.05 s
Pickup value of element 51P 2S13 30...80% FLA 50% FLA
Operate time of element 51P 2S14 2...600 s 2 s
Pickup value of element 46 2S15 0.10…0.50 x FLA 0.20 x FLA
Time constant of element 46
at IDMT characteristic
2S16 5...100 5
Restart disable value 2S17 5...500 s 5 s
Countdown rate of start-up
time counter
2S18 2...250 s/h 2 s/h
Operate time of CBFAIL 2S19 0.10...60.0 s 0.10 s
Alarm value RTD1A 2S20 0...200°C 0°C
Operate time RTD1A TDLY 2S26 1...100 s 1 s
Trip value RTD1T 2S32 0...200°C 0°C
Operate time RTD1T TDLY 2S38 1...100 s 1 s
Alarm value RTD2A 2S21 0...200°C 0°C
Operate time RTD2A TDLY 2S27 1...100 s 1 s
Trip value RTD2T 2S33 0...200°C 0°C
Operate time RTD2T TDLY 2S39 1...100 s 1 s
Alarm value RTD3A 2S22 0...200°C 0°C
Operate time RTD3A TDLY 2S28 1...100 s 1 s
Trip value RTD3T 2S34 0...200°C 0°C
Operate time RTD3T TDLY 2S40 1...100 s 1 s
Alarm value RTD4A 2S23 0...200°C 0°C
Operate time RTD4A TDLY 2S29 1...100 s 1 s
Trip value RTD4T 2S35 0...200°C 0°C
Operate time RTD4T TDLY 2S41 1...100 s 1 s
Alarm value RTD5A 2S24 0...200°C 0°C
Operate time RTD5A TDLY 2S30 1...100 s 1 s
Trip value RTD5T 2S36 0...200°C 0°C
Operate time RTD5T TDLY 2S42 1...100 s 1 s
Alarm value RTD6A 2S25 0...200°C 0°C
Operate time RTD6A TDLY 2S31 1...100 s 1 s
Trip value RTD6T 2S37 0...200°C 0°C
Operate time RTD6T TDLY 2S43 1...100 s 1 s
Trip value PTC1 2S44 0.1...15.0 kΩ 0.1 kΩ
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610REM 610
1MRS755537