Variable Group/
Channel 2
(R, W, P)
Setting range Default
setting
Customer’s
setting
Trip value PTC2 2S45 0.1...15.0 kΩ 0.1 kΩ
Checksum, SGF 1 2S61 0...255 0
Checksum, SGF 2 2S62 0...255 0
Checksum, SGF 3 2S63 0...255 2
Checksum, SGF 4 2S64 0...7 0
Checksum, SGF 5 2S65 0...255 0
Checksum, SGB 1 2S71 0...16383 0
Checksum, SGB 2 2S72 0...16383 0
Checksum, SGB 3 2S73 0...16383 0
Checksum, SGB 4 2S74 0...16383 0
Checksum, SGB 5 2S75 0...16383 0
Checksum, SGR 1 2S81 0...524287 6826
Checksum, SGR 2 2S82 0...524287 6826
Checksum, SGR 3 2S83 0...524287 0
Checksum, SGR 4 2S84 0...524287 9557
Checksum, SGR 5 2S85 0...524287 9557
Checksum, SGL 1 2S91 0...4194303 4
Checksum, SGL 2 2S92 0...4194303 8
Checksum, SGL 3 2S93 0...4194303 0
Checksum, SGL 4 2S94 0...4194303 0
Checksum, SGL 5 2S95 0...4194303 0
Checksum, SGL 6 2S96 0...4194303 0
Checksum, SGL 7 2S97 0...4194303 0
Checksum, SGL 8 2S98 0...4194303 0
Table 8.-3 Control parameters
Description Parameter
(channel 0)
Setting range Default
setting
Customer’s
setting
FLA secondary (protected
unit scaling factor)
V103 0.50...2.50 1.00
Rated frequency V104 50 or 60 Hz 60 Hz
Time setting range for
demand values in minutes
V105 0...999 min 10 min
Non-volatile memory
settings
V106 0...63 63
Time setting for disabling
new trip targets on the LCD
V108 0...999 min 60 min
Trip-circuit supervision V113 0 = not in use
1 = in use
150
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537