Switch Function Default setting
SGL1 SGL2 SGL3...8
SGL1...8/13 DI2 signal 0 0 0
SGL1...8/14 DI3 signal 0 0 0
SGL1...8/15 DI4 signal 0 0 0
SGL1...8/16 DI5 signal 0 0 0
SGL1...8/17 Alarm signal from element 49/38-1 0 0 0
SGL1...8/18 Trip signal from element 49/38-1 0 0 0
SGL1...8/19 Alarm signal from element 49/38-2 0 0 0
SGL1...8/20 Trip signal from element 49/38-2 0 0 0
SGL1...8/21 Trip signal from CBFAIL 0 0 0
SGL1...8/22 Disturbance recorder triggered 0 0 0
ΣSGL1...8 4 8 0
New trip target timer
The new trip target timer can be configured to allow a second trip target on the
LCD. When several protection elements trip, the first trip target will be displayed
until the time, as specified by the NEW TRIP IND. setting value, has expired. After
this, a new trip target can displace the old one. The basic protection functions are not
affected by the NEW TRIP IND. setting.
Table 5.1.4.12.-10 New trip target timer
Setting Description Setting range Default setting
New trip target New trip target timer in minutes 0...998 60
No new trip target allowed until the previous one
has been manually cleared
999
Non-volatile memory settings
The table below presents data which can be configured to be stored in the non-
volatile memory. All of the functions mentioned below can be selected separately
with switches 1...6 either via the HMI or the SPA bus.