Section 2 1MAC254287-MB B
DNP3 data mappings
12 REM615 ANSI
Point List Manual
Table 11: 50P:Three-phase non-directional overcurrent protection-high stage - instance 1 (PHHPTOC1
)
Table 12: 51G:Non-directional ground-fault protection-low stage - instance 1 (EFLPTOC1)
Table 13: 50G:Non-directional ground-fault protection-high stage - instance 1 (EFHPTOC1)
Table 14: 67/51N:Directional ground-fault protection-low stage - instance 1 (DEFLPTOC1)
Table 15: 59G:Residual overvoltage protection-instance 1 (ROVPTOV1)
Table 16: 59N:Residual overvoltage protection-instance 2 (ROVPTOV2)
Table 17: 27:Three-phase undervoltage protection-instance 1 (PHPTUV1)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 192 Class 1 and 0 Yes 50P Trip (Operate) LD0.PHHPTOC1.Op.general
BI 193 Class 1 and 0 Yes 50P Phase A Trip (Operate) LD0.PHHPTOC1.Op.phsA
BI 194 Class 1 and 0 Yes 50P Phase B Trip (Operate) LD0.PHHPTOC1.Op.phsB
BI 195 Class 1 and 0 Yes 50P Phase C Trip (Operate) LD0.PHHPTOC1.Op.phsC
BI Yes 196 Class 0 Yes 50P Enable Signal For Current Multiplier LD0.PHHPTOC1.InEnaMult.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 100 Class 1 and 0 Yes 51G Trip (Operate) LD0.EFLPTOC1.Op.general
BI Yes 101 Class 0 Yes 51G Enable Current Multiplier LD0.EFLPTOC1.InEnaMult.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 98 Class 1 and 0 Yes 50G Trip (Operate) LD0.EFHPTOC1.Op.general
BI Yes 99 Class 0 Yes 50G Enable Current Multiplier LD0.EFHPTOC1.InEnaMult.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 113 Class 1 and 0 Yes 67/51N Trip (Operate) LD0.DEFLPTOC1.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 257 Class 1 and 0 Yes 59G Trip (Operate) LD0.ROVPTOV1.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 258 Class 1 and 0 Yes 59N Trip (Operate) LD0.ROVPTOV2.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 273 Class 1 and 0 Yes 27 Trip (Operate) LD0.PHPTUV1.Op.general
BI 274 Class 1 and 0 Yes 27 Phase A Trip (Operate) LD0.PHPTUV1.Op.phsA
BI 275 Class 1 and 0 Yes 27 Phase B Trip (Operate) LD0.PHPTUV1.Op.phsB
BI 276 Class 1 and 0 Yes 27 Phase C Trip (Operate) LD0.PHPTUV1.Op.phsC