Section 3 1MAC254287-MB B
DNP3 protocol implementation
40 REM615 ANSI
Point List Manual
3.2 DNP3 implementation table
The following table identifies which object variations, function codes, and qualifiers the
IED supports in both request messages and response messages. For static
(non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 will be
responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are
always responded.
Table 93: Implementation table
Configurable
Sequential file transfer support:
Append file mode Yes No
Custom status code strings Yes No
Permissions field Yes No
File events assigned to class Yes No
File events send immediately Yes No
Multiple blocks in a fragment Yes No
Max number of files open 0
= Selected, = Not selected
DNP3 device profile document
OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with)
Object
number
Variation
number
Description Function codes (dec) Qualifier codes (hex) Function codes
(dec)
Qualifier codes
(hex)
1 0 Binary
input – any
variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
1
1 (default)
1
Binary
input
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2
1 2 Binary
input with
status
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2 0 Binary
input
change –
any
variation
1 (read) 06 (no range, or all)
07, 08 (limited qty)
2 1 Binary
input
change
without
time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
2 2 Binary
input
change
with time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)