1MAC254287-MB B Section 3
DNP3 protocol implementation
REM615 ANSI 39
Point List Manual
WRITE
binary
outputs
Never Always Sometimes Configurable
SELECT/OP
ERATE
Never Always Sometimes Configurable
DIRECT
OPERATE
Never Always Sometimes Configurable
DIRECT
OPERATE -
NO ACK
Never Always Sometimes Configurable
Count > 1
(Count > 1 is
accepted but
ignored)
Never Always Sometimes Configurable
Pulse on Never Always Sometimes Configurable
Pulse off Never Always Sometimes Configurable
Latch on Never Always Sometimes Configurable
Latch off Never Always Sometimes Configurable
Queue Never Always Sometimes Configurable
Clear queue Never Always Sometimes Configurable
The circuit breaker control model is configurable for either direct or SBO mode in the circuit breaker settings. If the operation mode does not
match the CROB, the returned CROB status is hardware error (4). All other control points may be controlled by either direct or SBO controls.
Reports binary input change events when no specific variation
requested:
Reports time-tagged binary input change events when no specific
variation requested:
Never Never
Only when time-tagged Binary input change with time
Only non-time-tagged Binary input change with relative time
Configurable to send one or the other Configurable
Sends unsolicited responses: Sends static data in unsolicited responses:
Never Never
Configurable When device restarts
Only certain objects When status flags change
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
function codes supported
No other options are permitted.
Default counter object/variation: Counters roll over at:
No counters reported No counters reported
Configurable Configurable (attach explanation)
Default object
Default variation:
16 bits
Point-by-point list attached 32 bits
Other value: _______
Point-by-point list attached
Sends multi-fragment responses:
Yes
No
DNP3 device profile document