EasyManua.ls Logo

ABB REM615 - Binary inputs DNP3 mapping

ABB REM615
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MAC254287-MB B Section 2
DNP3 data mappings
REM615 ANSI 13
Point List Manual
Table 18: 59:Three-phase overvoltage protection-instance 1 (PHPTOV1)
Table 19: 27PS:Positive-sequence undervoltage protection-instance 1 (PSPTUV1)
Table 20: 47:Negative-sequence overvoltage protection-instance 1 (NSPTOV1)
Table 21: 81:Frequency protection-instance 1 (FRPTRC1)
Table 22: 81:Frequency protection-instance 1 (FRPTOF1)
Table 23: 81:Frequency protection-instance 1 (FRPTUF1)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled IEC61850 Data Attribute Name Description
Scale
Factor
BI 265 Class 1 and 0 Yes LD0.PHPTOV1.Op.general 59 Trip (Operate)
BI 266 Class 1 and 0 Yes LD0.PHPTOV1.Op.phsA 59 Phase A Trip (Operate)
BI 267 Class 1 and 0 Yes LD0.PHPTOV1.Op.phsB 59 Phase B Trip (Operate)
BI 268 Class 1 and 0 Yes LD0.PHPTOV1.Op.phsC 59 Phase C Trip (Operate)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 263 Class 1 and 0 Yes 27PS Positive Sequence Under Voltage
1
LD0.PSPTUV1.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 261 Class 1 and 0 Yes 47 Trip (Operate) LD0.NSPTOV1.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI Yes 349 Class 0 Yes 81 Frequency Trip (Operate) LD0.FRPTRC1.Op.general
AI Yes 202 Class 0 Yes 81 Ratio Of Pickup (Start) Time / Trip
(Operate) Time Instance 1
100 LD0.FRPTRC1.StrDur.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 350 Class 1 and 0 Yes 81 Over-Frequency Trip (Operate) LD0.FRPTOF1.Op.general
AI Yes 203 Class 0 Yes 81 Ratio Of Pickup (Start) Time / Trip
(Operate) Time Overfrequency Instance
1
100 LD0.FRPTOF1.StrDur.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 351 Class 1 and 0 Yes 81 Under-Frequency Trip (Operate) LD0.FRPTUF1.Op.general
AI Yes 204 Class 0 Yes 81 Ratio Of Pickup (Start) Time / Trip
(Operate) Time Underfrequency
Instance 1
100 LD0.FRPTUF1.StrDur.mag.f