EasyManua.ls Logo

ABB REM615 - Page 21

ABB REM615
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MAC254287-MB B Section 2
DNP3 data mappings
REM615 ANSI 15
Point List Manual
Table 31: 66/51LRS:Motor start-up supervision (STTPMRI1)
Table 32: 46R:Phase reversal protection (PREVPTOC1)
Table 33: 49M:Thermal overload protection for motors (MPTTR1)
Table 34: 87M:Motor differential protection (MPDIF1)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 325 Class 1 and 0 Yes 66/51LRS Trip (Operate)/Trip Signal For
Thermal Stress
LD0.STTPMRI1.Op.general
BI Yes 626 Class 0 Yes 66/51LRS Reset number of motor
start-ups counter
LD0.STTPMRI1.RsStUpCnt.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 319 Class 1 and 0 Yes 46R Phase Reversal Protection LD0.PREVPTOC1.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 326 Class 1 and 0 Yes 49M Motor Thermal Alarm LD0.MPTTR1.AlmThm.general
BI 327 Class 1 and 0 Yes 49M Motor Trip (Operate) LD0.MPTTR1.Op.general
BI Yes 627 Class 0 Yes MPTTR1 MPTTR1 temperature LD0.MPTTR1.RsTmp.stVal
AI 191 Class 2 and 0 Yes 49M Thermal Level 100 LD0.MPTTR1.TmpRl.mag.f
AI Yes 192 Class 0 Yes 49M The Ambient Temperature Used In
The Calculation
100 LD0.MPTTR1.TmpUsed.mag.f
AI Yes 193 Class 0 Yes 49M Thermal Level At Beginning Of
Motor Startup
100 LD0.MPTTR1.ThmLevSt.mag.f
AI Yes 194 Class 0 Yes 49M Thermal Level At The End Of Motor
Startup Situation
100 LD0.MPTTR1.ThmLevEnd.mag.f
AI 195 Class 2 and 0 Yes 49M Estimated Time To Reset Of Block
Restart
0 LD0.MPTTR1.StrInhTms.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 332 Class 1 and 0 Yes 87M Motor Differential Protection LD0.MPDIF1.Op.general
BI 333 Class 1 and 0 Yes 87M Motor Differential Protection Phase
A
LD0.MPDIF1.Op.phsA
BI 334 Class 1 and 0 Yes 87M Motor Differential Protection Phase
B
LD0.MPDIF1.Op.phsB
BI 335 Class 1 and 0 Yes 87M Motor Differential Protection Phase
C
LD0.MPDIF1.Op.phsC
BI Yes 336 Class 0 Yes 87M Motor Differential Protection Block LD0.MPDIF1.BlkInSt.general
BI Yes 337 Class 0 Yes 87M Motor Differential Protection Block
Phase A
LD0.MPDIF1.BlkInSt.phsA
BI Yes 338 Class 0 Yes 87M Motor Differential Protection Block
Phase B
LD0.MPDIF1.BlkInSt.phsB
BI Yes 339 Class 0 Yes 87M Motor Differential Protection Block
Phase C
LD0.MPDIF1.BlkInSt.phsC

Other manuals for ABB REM615