Loading...
Section 2 1MAC254287-MB B
DNP3 data mappings
16 REM615 ANSI
Point List Manual
Table 35: 50BF:Circuit breaker failure protection-instance 1 (CCBRBRF1)
Table 36: 86/94-1:Master trip-instance 1 (TRPPTRC1)
Table 37: 86/94-2:Master trip-instance 2 (TRPPTRC2)
Table 38: AFD-1:Arc protection-instance 1 (ARCSARC11)
Table 39: AFD-1:Arc protection-instance 1 (ARCPTRC11)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 231 Class 1 and 0 Yes 50BF Recloser External Operation
Failure 1
LD0.CCBRBRF1.OpEx.general
BI 232 Class 1 and 0 Yes 50BF Recloser Retrip (Internal Trip) 1 LD0.CCBRBRF1.OpIn.general
BI Yes 233 Class 0 Yes 50BF Recloser Trip Start 1 LD0.CCBRBRF1.InStr.stVal
BI Yes 234 Class 0 Yes 50BF Recloser Close Position 1 LD0.CCBRBRF1.InPosCls.stVal
BI Yes 235 Class 0 Yes 50BF Recloser Faulty And Unable To
Trip 1
LD0.CCBRBRF1.InCBFlt.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 7 Class 1 and 0 Yes 86/94-1 Master Trip General Output 1 LD0.TRPPTRC1.Tr.general
BI 8 Class 1 and 0 Yes 86/94-1 Master Trip Operate Input 1 LD0.TRPPTRC1.Op.general
BI Yes 605 Class 0 Yes 86/94-1 Reset trip Lockout LD0.TRPPTRC1.LORs.stVal
BI 606 Class 1 and 0 Yes 86/94-1 Reset latched trip LD0.TRPPTRC1.TrRs.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 9 Class 1 and 0 Yes 86/94-2 Master Trip General Output 2 LD0.TRPPTRC2.Tr.general
BI 10 Class 1 and 0 Yes 86/94-2 Master Trip Operate Input 2 LD0.TRPPTRC2.Op.general
BI Yes 607 Class 0 Yes 86/94-2 Reset trip lockout LD0.TRPPTRC2.LORs.stVal
BI 608 Class 1 and 0 Yes 86/94-2 Reset latched trip LD0.TRPPTRC2.TrRs.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 286 Class 1 and 0 Yes AFD-1 Fault Arc Detected 1 LD0.ARCSARC11.FADet.stVal
BI Yes 287 Class 0 Yes AFD-1 Remote Fault Arc Detected 1 LD0.ARCSARC11.InRemFA.stVa
l
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 288 Class 1 and 0 Yes AFD-1 Arc Detected Trip (Operate) 1 LD0.ARCPTRC11.Op.general