1MAC254287-MB B Section 2
DNP3 data mappings
REM615 ANSI 17
Point List Manual
Table 40: AFD-2:Arc protection-instance 2 (ARCSARC21)
Table 41: AFD-2:Arc protection-instance 2 (ARCPTRC21)
Table 42: AFD-3:Arc protection-instance 3 (ARCSARC31)
Table 43: AFD-3:Arc protection-instance 3 (ARCPTRC31)
Table 44: MAP - 1:Multi-purpose protection-instance 1 (MAPGAPC1)
Table 45: MAP - 2:Multi-purpose protection-instance 2 (MAPGAPC2)
Table 46: MAP - 3:Multi-purpose protection-instance 3 (MAPGAPC3)
)
Table 47: 52:Circuit-breaker control-instance 1 (CBCILO1)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 289 Class 1 and 0 Yes AFD-2 Fault Arc Detected 2 LD0.ARCSARC21.FADet.stVal
BI Yes 290 Class 0 Yes AFD-2 Remote Fault Arc Detected 2 LD0.ARCSARC21.InRemFA.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 291 Class 1 and 0 Yes AFD-2 Arc Detected Trip (Operate) 2 LD0.ARCPTRC21.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 292 Class 1 and 0 Yes AFD-3 Fault Arc Detected 3 LD0.ARCSARC31.FADet.stVal
BI Yes 293 Class 0 Yes AFD-3 Remote Fault Arc Detected 3 LD0.ARCSARC31.InRemFA.stVa
l
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 294 Class 1 and 0 Yes AFD-3 Arc Detected Trip (Operate) 3 LD0.ARCPTRC31.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 386 Class 1 and 0 Yes MAP - 1 Multi-Purpose Protection 1 LD0.MAPGAPC1.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 387 Class 1 and 0 Yes MAP - 2 Multi-Purpose Protection 2 LD0.MAPGAPC2.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 388 Class 1 and 0 Yes MAP - 3 Multi-Purpose Protection 3 LD0.MAPGAPC3.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 589 Class 1 and 0 Yes 52 Breaker Interlock Enable Open 1 CTRL.CBCILO1.EnaOpn.stVal
BI 590 Class 1 and 0 Yes 52 Breaker Interlock Enable Close 1 CTRL.CBCILO1.EnaCls.stVal
BI 591 Class 1 and 0 Yes 52 Breaker Interlock Bypass 1 CTRL.CBCILO1.ItlByPss.stVal