Section 2 1MAC254287-MB B
DNP3 data mappings
18 REM615 ANSI
Point List Manual
Table 48: 52:Circuit-breaker control-instance 1 (CBCILO1)
Table 49: 52:Circuit-breaker control-instance 1 (CBCSWI1)
Table 50: 52:Circuit-breaker control-instance 1 (CBXCBR1)
Table 51: 2EST:Emergergency startup (ESMGAPC1)
Table 52: 52CM:Circuit-breaker condition monitoring-instance 1 (SSCBR1)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 589 Class 1 and 0 Yes 52 Breaker Interlock Enable Open 1 CTRL.CBCILO1.EnaOpn.stVal
BI 590 Class 1 and 0 Yes 52 Breaker Interlock Enable Close 1 CTRL.CBCILO1.EnaCls.stVal
BI 591 Class 1 and 0 Yes 52 Breaker Interlock Bypass 1 CTRL.CBCILO1.ItlByPss.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI Yes 592 Class 0 Yes 52 Breaker Switch Position Open CTRL.CBCSWI1.PosOpn.stVal
BI Yes 593 Class 0 Yes 52 Breaker Switch Position Closed CTRL.CBCSWI1.PosCls.stVal
BI Yes 594 Class 0 Yes 52 Breaker Switch Position valid CTRL.CBCSWI1.PosOk.stVal
AI 398 Class 2 and 0 Yes 52 Breaker Switch Position 1 0 CTRL.CBCSWI1.Pos.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 630 Class 1 and 0 Yes 52 Breaker Block Open CTRL.CBXCBR1.BlkOpn.stVal
BI 631 Class 1 and 0 Yes 52 Breaker Block Close CTRL.CBXCBR1.BlkCls.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI Yes 317 Class 0 Yes 62EST Emergency Start Required LD0.ESMGAPC1.RqEmgStr.stVal
BI 625 Class 1 and 0 Yes 62EST Emergency start LD0.ESMGAPC1.Str.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI Yes 11 Class 0 Yes 52CM Recloser Spring Charging Started
Input 1
LD0.SSCBR1.InSprChStr.stVal
BI Yes 12 Class 0 Yes 52CM Recloser Spring Charged Input 1 LD0.SSCBR1.InSprCha.stVal
BI Yes 13 Class 0 Yes 52CM Binary Pressure Input For Alarm 1 LD0.SSCBR1.InPresAlm.stVal
BI Yes 14 Class 0 Yes 52CM Binary Pressure Input For Lockout
Indication 1
LD0.SSCBR1.InPresLO.stVal
BI Yes 15 Class 0 Yes 52CM Posopen 1 LD0.SSCBR1.InPosOpn.stVal
BI Yes 16 Class 0 Yes 52CM Posclose 1 LD0.SSCBR1.InPosCls.stVal
BI 17 Class 1 and 0 Yes 52CM Recloser Open Travel Time
Exceeded Set Value 1
LD0.SSCBR1.OpnAlm.stVal
BI 18 Class 1 and 0 Yes 52CM Recloser Close Travel Time
Exceeded Set Value 1
LD0.SSCBR1.ClsAlm.stVal
BI 19 Class 1 and 0 Yes 52CM Spring Charging Time Has
Crossed The Set Value 1
LD0.SSCBR1.SprChaAlm.stVal