1MAC254287-MB B Section 2
DNP3 data mappings
REM615 ANSI 19
Point List Manual
BI 20 Class 1 and 0 Yes 52CM Number Of Recloser Operations
Exceeds Alarm Limit 1
LD0.SSCBR1.OpNumAlm.stVal
BI 21 Class 1 and 0 Yes 52CM Number Of Recloser Operations
Exceeds Lockout Limit 1
LD0.SSCBR1.OpNumLO.stVal
BI 22 Class 1 and 0 Yes 52CM Recloser Not Operated For Long
Time Alarm 1
LD0.SSCBR1.LonTmAlm.stVal
BI 23 Class 1 and 0 Yes 52CM Pressure Below Alarm Level 1 LD0.SSCBR1.PresAlm.stVal
BI 24 Class 1 and 0 Yes 52CM Pressure Below Lockout Level 1 LD0.SSCBR1.PresLO.stVal
BI Yes 25 Class 0 Yes 52CM Recloser Position Is Open 1 LD0.SSCBR1.PosOpn.stVal
BI Yes 26 Class 0 Yes 52CM Invalid Position 1 LD0.SSCBR1.PosIvd.stVal
BI Yes 27 Class 0 Yes 52CM Recloser Position Is Closed 1 LD0.SSCBR1.PosCls.stVal
BI Yes 28 Class 0 Yes 52CM Reset Accumulation Energy 1 LD0.SSCBR1.RsAccAPwr.stVal
BI Yes 29 Class 0 Yes 52CM Reset Input For Recloser
Remaining Life And Operation Counter 1
LD0.SSCBR1.RsCBWear.stVal
BI Yes 30 Class 0 Yes 52CM Reset Travel T 1 LD0.SSCBR1.RsTrvTm.stVal
BI Yes 31 Class 0 Yes 52CM Reset Spr.Charge T 1 LD0.SSCBR1.RsSprChaTm.stVal
BI 32 Class 1 and 0 Yes 52CM Accumulated Currents Power (Iyt)
Exceeded Alarm Limit 1
LD0.SSCBR1.APwrAlm.stVal
BI 33 Class 1 and 0 Yes 52CM Accumulated Currents Power (Iyt)
Exceeded Lockout Limit 1
LD0.SSCBR1.APwrLO.stVal
BI 34 Class 1 and 0 Yes 52CM Remaining Life Of Recloser
Exceeded Alarm Limit 1
LD0.SSCBR1.CBLifAlm.stVal
AI Yes 5 Class 0 Yes 52CM The Number Of Days Recloser
Has Been Inactive 1
0 LD0.SSCBR1.InaTmdCnt.stVal
AI Yes 6 Class 0 Yes 52CM Travel Time Of The Recloser
During Opening Operation 1
100 LD0.SSCBR1.TmmsOpn.mag.f
AI Yes 7 Class 0 Yes 52CM Travel Time Of The Recloser
During Closing Operation 1
100 LD0.SSCBR1.TmmsCls.mag.f
AI Yes 8 Class 0 Yes 52CM The Charging Time Of The
Recloser Spring 1
100 LD0.SSCBR1.TmsSprCha.mag.f
AI Yes 9 Class 0 Yes 52CM Phase A Recloser Monitoring
Remaining Life 1
0 LD0.SSCBR1.RmnLifPhA.stVal
AI Yes 10 Class 0 Yes 52CM Phase B Recloser Monitoring
Remaining Life 1
0 LD0.SSCBR1.RmnLifPhB.stVal
AI Yes 11 Class 0 Yes 52CM Phase C Recloser Monitoring
Remaining Life 1
0 LD0.SSCBR1.RmnLifPhC.stVal
AI Yes 12 Class 0 Yes 52CM Phase A Accumulated Currents
Power (Iyt) 1
100 LD0.SSCBR1.AccAPwrPhA.mag.f
AI Yes 13 Class 0 Yes 52CM Phase B Accumulated Currents
Power (Iyt) 1
100 LD0.SSCBR1.AccAPwrPhB.mag.f
AI Yes 14 Class 0 Yes 52CM Phase C Accumulated Currents
Power (Iyt) 1
100 LD0.SSCBR1.AccAPwrPhC.mag.f