Section 2 1MAC254287-MB B
DNP3 data mappings
20 REM615 ANSI
Point List Manual
Table 53: TCM-1:Trip circuit supervision-instance 1 (TCSSCBR1)
Table 54: TCM-2:Trip circuit supervision-instance 2 (TCSSCBR2)
Table 55: CCM:Current circuit supervision (CCRDIF1)
Table 56: 60:Fuse failure supervision-intance 1 (SEQRFUF1)
Table 57: OPTM-1:Runtime counter for machines and devices-instance 1 (MDSOPT1)
Table 58: OPTM-2:Runtime counter for machines and devices-instance 2 (MDSOPT2)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 295 Class 1 and 0 Yes TCM-1 Trip Circuit Supervision Alarm 1 LD0.TCSSCBR1.CirAlm.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 296 Class 1 and 0 Yes TCM-2 Trip Circuit Supervision Alarm 2 LD0.TCSSCBR2.CirAlm.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 297 Class 1 and 0 Yes CCM Current Circuit Supervision Trip
(Operate)
LD0.CCRDIF1.Op.general
BI 298 Class 1 and 0 Yes CCM Current Circuit Supervision Alarm LD0.CCRDIF1.Alm.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 299 Class 1 and 0 Yes 60 Three Phase Fuse Failure
Supervision
LD0.SEQRFUF1.Str3Ph.general
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 301 Class 1 and 0 Yes OPTM-1 Motor Runtime Counter
Operation Time Warning 1
LD0.MDSOPT1.OpTmWrn.stVal
BI 302 Class 1 and 0 Yes OPTM-1 Motor Runtime Counter
Operation Time Alarm 1
LD0.MDSOPT1.OpTmAlm.stVal
BI Yes 618 Class 0 Yes OPTM-1 operation t LD0.MDSOPT1.OpTmRs.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 303 Class 1 and 0 Yes OPTM-2 Motor Runtime Counter
Operation Time Warning 2
LD0.MDSOPT2.OpTmWrn.stVal
BI 304 Class 1 and 0 Yes OPTM-2 Motor Runtime Counter
Operation Time Alarm 2
LD0.MDSOPT2.OpTmAlm.stVal
BI Yes 619 Class 0 Yes OPTM-2 operation t LD0.MDSOPT2.OpTmRs.stVal