1MAC254287-MB B Section 2
DNP3 data mappings
REM615 ANSI 21
Point List Manual
Table 59: A-IB-IC:Three-phase current measurement-instance 1 (CMMXU1)
Table 60: IA-IB-IC:Three-phase current measurement-instance 1 (CMSTA1)
Table 61: IA-IB-IC (2):Three-phase current measurement-instance 2 (CMMXU2)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 161 Class 1 and 0 Yes IA IB IC (1) Current Source High Alarm LD0.CMMXU1.HiAlm.stVal
BI 162 Class 1 and 0 Yes IA IB IC (1) Current Source High
Warning
LD0.CMMXU1.HiWrn.stVal
BI 163 Class 1 and 0 Yes IA IB IC (1) Current Source Low Warning LD0.CMMXU1.LoWrn.stVal
BI 164 Class 1 and 0 Yes IA IB IC (1) Current Source Low Alarm LD0.CMMXU1.LoAlm.stVal
AI 42 Class 2 and 0 Yes IA IB IC (1) Phase A Mag (RMS) 100 LD0.CMMXU1.A.phsA.instCVal.m
ag.f
AI 43 Class 2 and 0 Yes IA IB IC (1) Phase A Mag
(Deadbanded)
100 LD0.CMMXU1.A.phsA.cVal.mag.f
AI 44 Class 2 and 0 Yes IA IB IC (1) Phase B Mag (RMS) 100 LD0.CMMXU1.A.phsB.instCVal.m
ag.f
AI 45 Class 2 and 0 Yes IA IB IC (1) Phase B Mag
(Deadbanded)
100 LD0.CMMXU1.A.phsB.cVal.mag.f
AI 46 Class 2 and 0 Yes IA IB IC (1) Phase C Mag (RMS) 100 LD0.CMMXU1.A.phsC.instCVal.m
ag.f
AI 47 Class 2 and 0 Yes IA IB IC (1) Phase C Mag
(Deadbanded)
100 LD0.CMMXU1.A.phsC.cVal.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI Yes 165 Class 0 Yes IA IB IC (1) Reset Max Demands LD0.CMSTA1.RecRs.stVal
AI Yes 48 Class 0 Yes IA IB IC (1) Phase A Average Demand 100 LD0.CMSTA1.AvAmpsA.mag.f
AI Yes 49 Class 0 Yes IA IB IC (1) Phase A Maximum Demand 100 LD0.CMSTA1.MaxAmpsA.mag.f
AI Yes 50 Class 0 Yes IA IB IC (1) Phase B Average Demand 100 LD0.CMSTA1.AvAmpsB.mag.f
AI Yes 51 Class 0 Yes IA IB IC (1) Phase B Maximum Demand 100 LD0.CMSTA1.MaxAmpsB.mag.f
AI Yes 52 Class 0 Yes IA IB IC (1) Phase C Average Demand 100 LD0.CMSTA1.AvAmpsC.mag.f
AI Yes 53 Class 0 Yes IA IB IC (1) Phase C Maximum Demand 100 LD0.CMSTA1.MaxAmpsC.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 166 Class 1 and 0 Yes IA IB IC (2) Current Source High Alarm LD0.CMMXU2.HiAlm.stVal
BI 167 Class 1 and 0 Yes IA IB IC (2) Current Source High
Warning
LD0.CMMXU2.HiWrn.stVal
BI 168 Class 1 and 0 Yes IA IB IC (2) Current Source Low Warning LD0.CMMXU2.LoWrn.stVal
BI 169 Class 1 and 0 Yes IA IB IC (2) Current Source Low Alarm LD0.CMMXU2.LoAlm.stVal
AI 54 Class 2 and 0 Yes IA IB IC (2) Phase A Mag (RMS) 100 LD0.CMMXU2.A.phsA.instCVal.m
ag.f
AI 55 Class 2 and 0 Yes IA IB IC (2) Phase A Mag
(Deadbanded)
100 LD0.CMMXU2.A.phsA.cVal.mag.f
AI 56 Class 2 and 0 Yes IA IB IC (2) Phase B Mag (RMS) 100 LD0.CMMXU2.A.phsB.instCVal.m
ag.f