1MAC254287-MB B Section 2
DNP3 data mappings
REM615 ANSI 23
Point List Manual
Table 64: I1-I2-I0 (2):Sequence current measurement-instance 2 (CSMSQI2)
Table 65: IG:Residual current measurement-instance 1 (RESCMMXU1)
Table 66: VA-VB-VC:Three-phase voltage measurement-instance 1 (VMMXU1)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
AI 92 Class 2 and 0 Yes I1-I2-I0 (2) Positive Sequence
Magnitude (RMS)
100 LD0.CSMSQI2.SeqA.c1.instCVal.mag.f
AI 93 Class 2 and 0 Yes I1-I2-I0 (2) Positive Sequence
Magnitude (Deadband)
100 LD0.CSMSQI2.SeqA.c1.cVal.mag.f
AI 94 Class 2 and 0 Yes I1-I2-I0 (2) Negative Sequence
Magnitude (RMS)
100 LD0.CSMSQI2.SeqA.c2.instCVal.mag.f
AI 95 Class 2 and 0 Yes I1-I2-I0 (2) Negative Sequence
Magnitude (Deadband)
100 LD0.CSMSQI2.SeqA.c2.cVal.mag.f
AI 96 Class 2 and 0 Yes I1-I2-I0 (2) Zero Sequence
Magnitude (RMS)
100 LD0.CSMSQI2.SeqA.c3.instCVal.mag.f
AI 97 Class 2 and 0 Yes I1-I2-I0 (2) Zero Sequence
Magnitude (Deadband)
100 LD0.CSMSQI2.SeqA.c3.cVal.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 171 Class 1 and 0 Yes IG High Trip (Operate) LD0.RESCMMXU1.HiAlm.stVal
BI 172 Class 1 and 0 Yes IG High Warning LD0.RESCMMXU1.HiWrn.stVal
AI 66 Class 2 and 0 Yes IG Magnitude (RMS) 100 LD0.RESCMMXU1.A.res.instCVal.mag.f
AI 67 Class 2 and 0 Yes IG Magnitude (deadbanded) 100 LD0.RESCMMXU1.A.res.cVal.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 176 Class 1 and 0 Yes VA VB VC High Trip (Operate) LD0.VMMXU1.HiAlm.stVal
BI 177 Class 1 and 0 Yes VA VB VC High Warning LD0.VMMXU1.HiWrn.stVal
BI 178 Class 1 and 0 Yes VA VB VC Low Warning LD0.VMMXU1.LoWrn.stVal
BI 179 Class 1 and 0 Yes VA VB VC Low Trip (Operate) LD0.VMMXU1.LoAlm.stVal
AI 68 Class 2 and 0 Yes VA VB VC Phase A Mag 100 LD0.VMMXU1.PhV.phsA.cVal.mag.f
AI 69 Class 2 and 0 Yes VA VB VC Phase B Mag 100 LD0.VMMXU1.PhV.phsB.cVal.mag.f
AI 70 Class 2 and 0 Yes VA VB VC Phase C Mag 100 LD0.VMMXU1.PhV.phsC.cVal.mag.f
AI 71 Class 2 and 0 Yes VA VB VC Phase AB Mag
(RMS)
100 LD0.VMMXU1.PPV.phsAB.instCVal.mag.f
AI 72 Class 2 and 0 Yes VA VB VC Phase AB Mag
(Deadband)
100 LD0.VMMXU1.PPV.phsAB.cVal.mag.f
AI 73 Class 2 and 0 Yes VA VB VC Phase BC Mag
(RMS)
100 LD0.VMMXU1.PPV.phsBC.instCVal.mag.f
AI 74 Class 2 and 0 Yes VA VB VC Phase BC Mag
(Deadband)
100 LD0.VMMXU1.PPV.phsBC.cVal.mag.f
AI 75 Class 2 and 0 Yes VA VB VC Phase CA Mag
(RMS)
100 LD0.VMMXU1.PPV.phsCA.instCVal.mag.f
AI 76 Class 2 and 0 Yes VA VB VC Phase CA Mag
(Deadband)
100 LD0.VMMXU1.PPV.phsCA.cVal.mag.f

Other manuals for ABB REM615