EasyManua.ls Logo

ABB REM615 - Page 30

ABB REM615
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 2 1MAC254287-MB B
DNP3 data mappings
24 REM615 ANSI
Point List Manual
Table 67: VG:Residual voltage measurement-instance 1 (RESVMMXU1)
Table 68: V1-V2-V0:Sequence voltage measurement-instance 1 (VSMSQI1)
Table 69: SP-SE:Single-phase power and energy measurement-instance 1 (SPEMMXU1)
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI 174 Class 1 and 0 Yes VG High Alarm LD0.RESVMMXU1.HiAlm.stVal
BI 175 Class 1 and 0 Yes VG High Warning LD0.RESVMMXU1.HiWrn.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
AI 98 Class 2 and 0 Yes V1 V2 V0 Positive Sequence Mag
(RMS)
100 LD0.VSMSQI1.SeqV.c1.instCVal.mag.f
AI 99 Class 2 and 0 Yes V1 V2 V0 Positive Sequence Mag
(Deadband)
100 LD0.VSMSQI1.SeqV.c1.cVal.mag.f
AI 100 Class 2 and 0 Yes V1 V2 V0 Negative Sequence
Mag (RMS)
100 LD0.VSMSQI1.SeqV.c2.instCVal.mag.f
AI 101 Class 2 and 0 Yes V1 V2 V0 Negative Sequence
Mag (Deadband)
100 LD0.VSMSQI1.SeqV.c2.cVal.mag.f
AI 102 Class 2 and 0 Yes V1 V2 V0 Zero Sequence Mag
(RMS)
100 LD0.VSMSQI1.SeqV.c3.instCVal.mag.f
AI 103 Class 2 and 0 Yes V1 V2 V0 Zero Sequence Mag
(Deadband)
100 LD0.VSMSQI1.SeqV.c3.cVal.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
AI 370 Class 2 and 0 Yes SP SE Phase A Active Power 1 100 LD0.SPEMMXU1.W.phsA.cVal.mag.f
AI 371 Class 2 and 0 Yes SP SE Phase B Active Power 1 100 LD0.SPEMMXU1.W.phsB.cVal.mag.f
AI 372 Class 2 and 0 Yes SP SE Phase C Active Power 1 100 LD0.SPEMMXU1.W.phsC.cVal.mag.f
AI 373 Class 2 and 0 Yes SP SE Phase A Reactive Power 1 100 LD0.SPEMMXU1.VAr.phsA.cVal.mag.f
AI 374 Class 2 and 0 Yes SP SE Phase B Reactive Power 1 100 LD0.SPEMMXU1.VAr.phsB.cVal.mag.f
AI 375 Class 2 and 0 Yes SP SE Phase C Reactive Power 1 100 LD0.SPEMMXU1.VAr.phsC.cVal.mag.f
AI 376 Class 2 and 0 Yes SP SE Phase A Apparent Power 1 100 LD0.SPEMMXU1.VA.phsA.cVal.mag.f
AI 377 Class 2 and 0 Yes SP SE Phase B Apparent Power 1 100 LD0.SPEMMXU1.VA.phsB.cVal.mag.f
AI 378 Class 2 and 0 Yes SP SE Phase C Apparent Power 1 100 LD0.SPEMMXU1.VA.phsC.cVal.mag.f
AI 379 Class 2 and 0 Yes SP SE Average A Power Factor 1 100 LD0.SPEMMXU1.PF.phsA.cVal.mag.f
AI 380 Class 2 and 0 Yes SP SE Average B Power Factor 1 100 LD0.SPEMMXU1.PF.phsB.cVal.mag.f
AI 381 Class 2 and 0 Yes SP SE Average C Power Factor 1 100 LD0.SPEMMXU1.PF.phsC.cVal.mag.f

Other manuals for ABB REM615