Section 2 1MAC254287-MB B
DNP3 data mappings
32 REM615 ANSI
Point List Manual
Table 88: DFR:Disturbance recorder (RDRE1)
Table 89: FR:Fault recorder (FLTMSTA1)
BI 401 Class 1 and 0 Yes MV-2 Gen. Purp. Q11 LD0.MVGAPC2.Q3.stVal
BI 402 Class 1 and 0 Yes MV-2 Gen. Purp. Q12 LD0.MVGAPC2.Q4.stVal
BI 403 Class 1 and 0 Yes MV-2 Gen. Purp. Q13 LD0.MVGAPC2.Q5.stVal
BI 404 Class 1 and 0 Yes MV-2 Gen. Purp. Q14 LD0.MVGAPC2.Q6.stVal
BI 405 Class 1 and 0 Yes MV-2 Gen. Purp. Q15 LD0.MVGAPC2.Q7.stVal
BI 406 Class 1 and 0 Yes MV-2 Gen. Purp. Q16 LD0.MVGAPC2.Q8.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI Yes 601 Class 0 Yes DFR Disturbance Recording
Triggered
DR.RDRE1.RcdTrg.stVal
BI Yes 602 Class 0 Yes DFR Clear Disturbance Recorder
Memory
DR.RDRE1.MemClr.stVal
BI 603 Class 1 and 0 Yes DFR Disturbance Recording Made DR.RDRE1.RcdMade.stVal
AI Yes 400 Class 0 Yes DFR Number Of Recordings 0 DR.RDRE1.FltNum.stVal
AI Yes 401 Class 0 Yes DFR Recording Memory Used % 0 DR.RDRE1.MemUsed.stVal
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI Yes 185 Class 0 Yes Reset Fault Records LD0.FLTMSTA1.RecRs.stVal
AI 116 Class 2 and 0 Yes Fault Record Operation Counter 1 LD0.FLTMSTA1.OpCnt.stVal
AI 117 Class 2 and 0 Yes Last Fault: Max Start Duration Of All
Stages During The Fault
1 LD0.FLTMSTA1.StrDur.mag.f
AI 118 Class 2 and 0 Yes Maximum differential current phase A 100 LD0.FLTMSTA1.MxDifAClcA.mag.f
AI 119 Class 2 and 0 Yes Maximum differential current phase B 100 LD0.FLTMSTA1.MxDifAClcB.mag.f
AI 120 Class 2 and 0 Yes Maximum differential current phase C 100 LD0.FLTMSTA1.MxDifAClcC.mag.f
AI 121 Class 2 and 0 Yes Maximum bias current phase A 100 LD0.FLTMSTA1.MxRstAClcA.mag.f
AI 122 Class 2 and 0 Yes Maximum bias current phase B 100 LD0.FLTMSTA1.MxRstAClcB.mag.f
AI 123 Class 2 and 0 Yes Maximum bias current phase C 100 LD0.FLTMSTA1.MxRstAClcC.mag.f
AI 124 Class 2 and 0 Yes Differential current phase A 100 LD0.FLTMSTA1.DifAmpsA.mag.f
AI 125 Class 2 and 0 Yes Differential current phase B 100 LD0.FLTMSTA1.DifAmpsB.mag.f
AI 126 Class 2 and 0 Yes Differential current phase C 100 LD0.FLTMSTA1.DifAmpsC.mag.f
AI 127 Class 2 and 0 Yes Bias current phase A 100 LD0.FLTMSTA1.RstAmpsA.mag.f
AI 128 Class 2 and 0 Yes Bias current phase B 100 LD0.FLTMSTA1.RstAmpsB.mag.f
AI 129 Class 2 and 0 Yes Bias current phase C 100 LD0.FLTMSTA1.RstAmpsC.mag.f
AI 130 Class 2 and 0 Yes Differential current residual 100 LD0.FLTMSTA1.DifAmpsN.mag.f
AI 131 Class 2 and 0 Yes Bias current residual 100 LD0.FLTMSTA1.RstAmpsN.mag.f
AI 132 Class 2 and 0 Yes Last Fault: Max Phase A Current
Magnitude
1 LD0.FLTMSTA1.MaxAmpsA.mag.f