1MAC254287-MB B Section 2
DNP3 data mappings
REM615 ANSI 33
Point List Manual
AI 133 Class 2 and 0 Yes Last Fault: Max Phase B Current
Magnitude
1 LD0.FLTMSTA1.MaxAmpsB.mag.f
AI 134 Class 2 and 0 Yes Last Fault: Max Phase C Current
Magnitude
1 LD0.FLTMSTA1.MaxAmpsC.mag.f
AI 135 Class 2 and 0 Yes Last Fault: Max Neutral Current
Magnitude
1 LD0.FLTMSTA1.MaxAmpsN.mag.f
AI 136 Class 2 and 0 Yes Last Fault: Phase A Current
Magnitude
1 LD0.FLTMSTA1.AmpsA.mag.f
AI 137 Class 2 and 0 Yes Last Fault: Phase B Current
Magnitude
1 LD0.FLTMSTA1.AmpsB.mag.f
AI 138 Class 2 and 0 Yes Last Fault: Phase C Current
Magnitude
1 LD0.FLTMSTA1.AmpsC.mag.f
AI 139 Class 2 and 0 Yes Last Fault: Neutral Current
Magnitude
1 LD0.FLTMSTA1.AmpsN.mag.f
AI 140 Class 2 and 0 Yes Last Fault: Calculated Residual
Current Magnitude
1 LD0.FLTMSTA1.AmpsNClc.mag.f
AI 141 Class 2 and 0 Yes Last Fault: Positive Sequence
Current Mag.
1 LD0.FLTMSTA1.AmpsPsSeq.mag.f
AI 142 Class 2 and 0 Yes Last Fault: Negative Sequence
Current Mag.
1 LD0.FLTMSTA1.AmpsNgSeq.mag.f
AI 143 Class 2 and 0 Yes Maximum phase A current (b) 100 LD0.FLTMSTA1.MaxAmpsAb.mag.f
AI 144 Class 2 and 0 Yes Maximum phase B current (b) 100 LD0.FLTMSTA1.MaxAmpsBb.mag.f
AI 145 Class 2 and 0 Yes Maximum phase C current (b) 100 LD0.FLTMSTA1.MaxAmpsCb.mag.f
AI 146 Class 2 and 0 Yes Maximum residual current (b) 100 LD0.FLTMSTA1.MaxAmpsNb.mag.f
AI 147 Class 2 and 0 Yes Phase A current (b) 100 LD0.FLTMSTA1.AmpsAb.mag.f
AI 148 Class 2 and 0 Yes Phase B current (b) 100 LD0.FLTMSTA1.AmpsBb.mag.f
AI 149 Class 2 and 0 Yes Phase C current (b) 100 LD0.FLTMSTA1.AmpsCb.mag.f
AI 150 Class 2 and 0 Yes Residual current (b) 100 LD0.FLTMSTA1.AmpsNb.mag.f
AI 151 Class 2 and 0 Yes Calculated residual current (b) 100 LD0.FLTMSTA1.AmpsNClcb.mag.f
AI 152 Class 2 and 0 Yes Positive sequence current (b) 100 LD0.FLTMSTA1.AmpsPsSeqb.mag.f
AI 153 Class 2 and 0 Yes Negative sequence current (b) 100 LD0.FLTMSTA1.AmpsNgSeqb.mag.f
AI 154 Class 2 and 0 Yes Last Fault: Phase A Voltage
Magnitude
1 LD0.FLTMSTA1.VoltsA.mag.f
AI 155 Class 2 and 0 Yes Last Fault: Phase B Voltage
Magnitude
1 LD0.FLTMSTA1.VoltsB.mag.f
AI 156 Class 2 and 0 Yes Last Fault: Phase C Voltage
Magnitude
1 LD0.FLTMSTA1.VoltsC.mag.f
AI 157 Class 2 and 0 Yes Last Fault: Phase AB Voltage
Magnitude
1 LD0.FLTMSTA1.VoltsAB.mag.f
AI 158 Class 2 and 0 Yes Last Fault: Phase BC Voltage
Magnitude
1 LD0.FLTMSTA1.VoltsBC.mag.f
AI 159 Class 2 and 0 Yes Last Fault: Phase CA Voltage
Magnitude
1 LD0.FLTMSTA1.VoltsCA.mag.f
AI 160 Class 2 and 0 Yes Last Fault: Measured Residual
Voltage Magnitude
1 LD0.FLTMSTA1.VoltsN.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name