Section 2 1MAC254287-MB B
DNP3 data mappings
34 REM615 ANSI
Point List Manual
Table 90: FLO:Fault location (DRFLO1)
AI 161 Class 2 and 0 Yes Last Fault: Zero Sequence Voltage
Magnitude
1 LD0.FLTMSTA1.VZroSeq.mag.f
AI 162 Class 2 and 0 Yes Last Fault: Positive Sequence
Voltage Magnitude
1 LD0.FLTMSTA1.VPsSeq.mag.f
AI 163 Class 2 and 0 Yes Last Fault: Negative Sequence
Voltage Magnitude
1 LD0.FLTMSTA1.VNgSeq.mag.f
AI 164 Class 2 and 0 Yes Phase A voltage (b) 100 LD0.FLTMSTA1.VoltsAb.mag.f
AI 165 Class 2 and 0 Yes Phase B voltage (b) 100 LD0.FLTMSTA1.VoltsBb.mag.f
AI 166 Class 2 and 0 Yes Phase C voltage (b) 100 LD0.FLTMSTA1.VoltsCb.mag.f
AI 167 Class 2 and 0 Yes Phase A to phase B voltage (b) 100 LD0.FLTMSTA1.VoltsABb.mag.f
AI 168 Class 2 and 0 Yes Phase B to phase C voltage (b) 100 LD0.FLTMSTA1.VoltsBCb.mag.f
AI 169 Class 2 and 0 Yes Phase C to phase A voltage (b) 100 LD0.FLTMSTA1.VoltsCAb.mag.f
AI 170 Class 2 and 0 Yes Residual voltage (b) 100 LD0.FLTMSTA1.VoltsNb.mag.f
AI 171 Class 2 and 0 Yes Zero sequence voltage (b) 100 LD0.FLTMSTA1.VZroSeqb.mag.f
AI 172 Class 2 and 0 Yes Positive sequence voltage (b) 100 LD0.FLTMSTA1.VPsSeqb.mag.f
AI 173 Class 2 and 0 Yes Negative sequence voltage (b) 100 LD0.FLTMSTA1.VNgSeqb.mag.f
AI 175 Class 2 and 0 Yes Last Fault: I2/I1 Ratio Fault 1 LD0.FLTMSTA1.PDNS1MxRat.mag.f
AI 176 Class 2 and 0 Yes Last Fault: Frequency At The Time
The Fault Is Cleared
1 LD0.FLTMSTA1.Hz.mag.f
AI 177 Class 2 and 0 Yes Last Fault: Frequency Gradient At
The Time The Fault Is Cleared
1 LD0.FLTMSTA1.HzS.mag.f
AI 178 Class 2 and 0 Yes Last Fault: Conductance Yo 1 LD0.FLTMSTA1.CondN.mag.f
AI 179 Class 2 and 0 Yes Last Fault: Susceptance Yo 1 LD0.FLTMSTA1.SusN.mag.f
AI 403 Class 2 and 0 Yes Distance to fault measured in pu 1 LD0.FLTMSTA1.FltDisKm.mag.f
AI 404 Class 2 and 0 Yes Active Setting at time of Fault 1 LD0.FLTMSTA1.ActSG.stVal
AI 405 Class 2 and 0 Yes Last Fault: Max Temperature 1 LD0.FLTMSTA1.MaxTmpRl.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
DNP
Object
Type
No
Event
Point
Index
DNP Class Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI Yes 541 Class 0 Yes FLO Relay Trip LD0.DRFLO1.Tr.general
AI 225 Class 2 and 0 Yes FLO Distance to fault measured in
Km/Miles
1 LD0.DRFLO1.FltDisKm.mag.f