EasyManuals Logo

ABB REX 521 Technical Reference Manual, General

ABB REX 521
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
40
1MRS 751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
“Net Messages” state
The parameter should be in the “Net Messages” state if the time synchronization is
taken from one of the following sources:
SPA bus
Time synchronization is received from the SPA master device.
IEC 60870-5-103 bus
Time synchronization is received from the IEC 60870-5-103 master device.
LON bus in the following cases:
Time synchronization message is received from the SNVT_Timestamp input
network variable.
Time synchronization message is received from the nv_warning/nv_clock
input network variables.
Some additional comments:
The SNVT_Timestamp network variable selector is 0x2FF5 (fixed).
The nv_warning and nv_clock selector values are 0x2FFE and 0x2FFF
respectively (also fixed).
“X3.1.2 Input” state
Synchronization is received from the digital input DI9. The input can act either as a
minute or a second synchronization input depending on the setting of the parameter
Sync.rounding. Furthermore, it is possible via the parameter
Sync.trigg.slope to set the pulse edge (positive or negative) which triggers
the synchronization.
Accuracy
When there is no external synchronization, the roaming time is better than 3 ms/min.
It is recommended that the relay is synchronized once a second in order to achieve
optimal accuracy.
4.1.14. Display panel (HMI)
The front panel of the relay includes:
A 2 X 16 character LCD (2 rows)
Three protection indication LEDs
Eight alarm LEDs
Arrow buttons for menu navigation
Optically isolated serial communication port
Additional features of the display:
Contrast adjustment with temperature compensation
Backlight control

Table of Contents

Other manuals for ABB REX 521

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REX 521 and is the answer not in the manual?

ABB REX 521 Specifications

General IconGeneral
BrandABB
ModelREX 521
CategoryOther
LanguageEnglish

Related product manuals