1MRS751802-MUM
REX 521
163
Protection Relay
Technical Reference Manual, Standard Configurations
Fig. 9.3.5.-1 Phase overcurrent blocking signal overview diagram for the first
three application examples with trip signals from the different
overcurrent stages
9.4. Outgoing feeder, Basic B02
9.4.1. Features
This application example describes an outgoing feeder of a single busbar including:
• Auto-reclosure function
• Overcurrent protection
• Non-directional earth fault protection
• Phase discontinuity protection
• Thermal overload protection for cable/line
The network is either resistance or solidly earthed. Three-phase current
measurement is established with a set of current transformers and the neutral current
is measured in a residual connection.
3I>
3I>>
3I>>>
3I>
3I>>
3I>>>
3I>
3I>>
3I>>>
REX521
REX521
REX521
BS
BS
START 3I>>
START 3I>>
TRIP
TRIP
TRIP
Application
example 1
(8.1.)
Application
example 3
(8.3.)
Application
example 2
(8.2.)
PhaseOverCurr