Fig. 9.3.5.-1 Phase overcurrent blocking signal overview diagram for the first
three application examples with trip signals from the different
overcurrent stages
9.4. Outgoing feeder, Basic B02
9.4.1. Features
This application example describes an outgoing feeder of a single busbar including:
Auto-reclosure function
Overcurrent protection
Non-directional earth fault protection
Phase discontinuity protection
Thermal overload protection for cable/line
The network is either resistance or solidly earthed. Three-phase current
measurement is established with a set of current transformers and the neutral current
is measured in a residual connection.
3I>
3I>>
3I>>>
3I>
3I>>
3I>>>
3I>
3I>>
3I>>>