1MRS751802-MUM
REX 521
47
Protection Relay
Technical Reference Manual, Standard Configurations
3.3.5. Standard configuration H05
3.3.5.1. Features
Three-phase non-directional overcurrent protection with three stages
Non-directional earth fault protection with three stages
Three-phase overvoltage protection with two stages
Three-phase undervoltage protection with two stages
Residual overvoltage protection with three stages
Three-phase transformer inrush and motor start-up current detector
Three-phase thermal overload protection for devices
Supervision function for energizing current input circuit
Supervision function for energizing voltage input circuit
Current waveform distortion measurement
Voltage waveform distortion measurement
Three-phase current measurement
Neutral current measurement
Three phase voltage measurements
Residual voltage measurement
System frequency measurement
Three-phase power and energy measurement
Calculation of the accumulated electric breaker wear of the circuit breaker (CB)
Transient disturbance recorder
Trip-circuit supervision
Delayed trip output for the circuit-breaker failure protection (CBFP) function
Circuit breaker control with indication
Lockout function
Object indication
Logic control position selector
User-configurable I/Os
•Interlocking
User-configurable alarm LEDs
It is possible to record 16 digital signals in the disturbance recorder.