EasyManua.ls Logo

ABB REX 521 - Page 18

ABB REX 521
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
1MRS751802-MUM
Protection Relay
Technical Reference Manual, Standard Configurations
REX 521
Io>>>->
4
DEF2Inst 67N x x x x x x
3I>-> DOC6Low 67 x
x
3
x
3I>>-> DOC6High 67 x
x
3
3U> OV3Low 59 x x x x x
3U>> OV3High 59 x x x x x
3U< UV3Low 27 x x x x x
3U<< UV3High 27 x x x x x
3I2f> Inrush3 68 x x x x x x x x x x x
Iub> CUB3Low 46 x x x x x x x x
3Ith> TOL3Cab 49F x x x x x x x x
O->I AR5Func 79 x x x x x x x
Uo> ROV1Low 59N x x x x
Uo>> ROV1High 59N x x x x
Uo>>> ROV1Inst 59N x x x x
f1 Freq1St1 81U/81O x x x x x
f2 Freq1St2 81U/81O x x
SYNC1 SCVCSt1 25 x x
Is2t n< MotStart 48, 14, 66 x
3I() PREV3 46R x
I2> NPS3Low 46 x
I2>> NPS3High 46 x
3I< NUC3St1 37 x
FUSEF FuseFail 60 x
3Ithdev> Tol3Dev 49M x x x
U1<U1U2> PSV3St1 27, 47, 59 x
Control functions
I<->O CB1COCB1 xxxx x x x x xxx x x
I<->O IND1 COIND1 x x x x x x x x x x x x x
I<->O IND2 COIND2 x x x x x x x x x x x x x
I<->O IND3 COIND3
x
5
I<->O POS COLOCAT x x x x x x x x x x x x x
ALARM1-8 MMIALAR1-8 x x x x x x x x x x x x x
Measurement
3I MECU3A x x x x x x x x x x x x x
Io MECU1A x x x x x x x x x x x x x
Uo MEVO1A x x x x x x x x x x x
DREC MEDREC x x x x x x x x x x x x x
3U MEVO3A x x x x x x x x x
3U_B MEVO3B xx
fMEFR1 xxxxxxxxx
PQE MEPE7 x x x x x x x x x
Table 2.-1 Standard configurations for REX 521 (Continued)
HW versions Basic Medium High/Sensor
Standard configurations B01 B02 M01 M02
H01
1,6,7
H02
7
H03
6,7
H04
7
H05
7
H06 H07
H08
7,8
H09
7,8
Function
blocks
FB name
(in CD-ROM)
IEEE
device
number

Table of Contents

Other manuals for ABB REX 521

Related product manuals