EasyManua.ls Logo

ABB RMC-100 - 5 Power the RMC; Power on Sequence; Table 4-11: TFIO Combo Digital Module and Extended; Table 4-12: TFIO Thermocouple Module

ABB RMC-100
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2105551MNAD | RMC-100 | 17
Table 4-11: TFIO combo digital module and extended
J1
J2
J3
J4
1
POINT 1 SIG
POINT 3 SIG
POINT 5 SIG
POINT 7 SIG
2
POINT 1 GND
POINT 3 GND
POINT 5 GND
POINT 7 GND
3
POINT 2 SIG
POINT 4 SIG
POINT 6 SIG
POINT 8 SIG
4
POINT 2 GND
POINT 4 GND
POINT 6 GND
POINT 8 GND
Table 4-12: TFIO thermocouple module
J1
J2
J3
J4
1
Shield
Shield
Shield
Shield
2
TC1 (J-Wht/K-Yel)
TC2 (J-Wht/K-Yel)
TC3 (J-Wht/K-Yel)
TC4 (J-Wht/K-Yel)
3
TC1 Red (-)
TC2 Red (-)
TC3 Red (-)
TC4 Red (-)
4
Shield
Shield
Shield
Shield
Table 4-13: TFIO RTD module
J1
J2
J3
J4
1
OUT
OUT
OUT
OUT
2
(+)
(+)
(+)
(+)
3
(-)
(-)
(-)
(-)
4
IN
IN
IN
IN
See section 8.6 to configure the TFIO interfaces.
5 Power the RMC
This section describes two modes for powering the controller:
Battery mode: Power is supplied by a 12 volt battery with a charger (see section 5.2
.)
External power mode: Power is supplied by an external power source (see section 5.3.)
Review section 5.1, follow the instructions for the appropriate power mode, then continue to section 5.4
Lithium battery.
NOTICE
Equipment damage.
Power compatibility for TFIO modules depends on module
generation
:
Older green modules must only use 12 Vdc.
M2 modules and newer gray modules can use 12 or 24 Vdc.
A combination of green modules and M2 modules or gra
y modules must only use 12
Vdc.
5.1 Power on sequence
The RMC power on sequence is initiated as soon as power is connected. The following information may be
displayed on the LCD as the controller completes its startup:
ABB TOTALFLOW RMC-100: identifies the controller name and model
BOOT 2105412-XXX: indicates the version of the boot software
OS 2105411-XXX: indicates the version of the operating system
Super CAP Charged: indicates if the super capacitor is charged (see section 5.1.1
.)
APP 2105457-XXX: indicates the flash version
IMPORTANT NOTE:
The scrolling duration of the displayed items may vary. When the
DATE/TIME displays, the power on sequence is completed.