2105551MNAD | RMC-100 | 23
Figure 6-4: Connection setup when using Ethernet for local communication
6. Click Close to exit connection setup and return to the main PCCU screen.
7. Click Entry on the top PCCU tool bar to establish connection.
6.3 Configure the station
To configure the station:
1. At the PCCU32 Entry screen, click the station ID name in the top node of the navigation tree. The
Station Setup tab displays.
2. Set up the basic settings identified in Table 6-1
.
Table 6-1: Required Station setup
The station identifier code uniquely identifies each station. If
running a multiple tube station, the station ID is the same for
all tubes on the RMC. If left blank on a single tube device, the
station ID will be the same as the device ID.
The location identifier describes the location, such as the county
name or a road number. Not mandatory.
Date and time must be set correctly and should agree with the
collection equipment if measurement tubes are
instantiated.
3. Verify the Lithium Battery Status is OK in a green bar (Figure 6-5). If the status is “Low Voltage”
or “Not Connected”, the field background color is red. Refer to Troubleshooting in the RMC-100
user manual to determine and resolve the problem before continuing with startup instructions.