DP-V0 communication
55
Example 1: Reading a drive parameter (or data set)
To determine the parameter number and subindex for drive
parameter reading, multiply the parameter number by one
hundred and then convert it to hexadecimal. The low byte is the
subindex (IND), and the high byte is the parameter number (PNU).
For example reading parameter 84.11 INPUT 1 from the drive:
84.11 × 100 = 8411 = 20DBh.
Parameter number is 20 and subindex is DB.
Req6020DB0000000000047F34150000000000000000
Resp 40 20 DB 00 00 00 00 64 03 37 34 15 00 00 00 00 00 00 00 00
CW REF
Parameter Number (20h)
Request (Read parameter value [array])
Subindex (DBh)*
PZD3 PZD4 PZD5 PZD6
SW ACT PZD3 PZD4 PZD5 PZD6
Parameter Value (100 Dec)
Parameter Number (20h)
Response (Change parameter value [array])
Subindex (DBh)*
*2nd byte reserved